Lennox Climatic 50 User Manual page 72

Table of Contents

Advertisement

Main
screen
Code
Description
Code
3-Setting
3000
1-General
3100
2-Schedule
3200
3-Control
3300
CLIMATIC 50 user manual – chillers ranges
Description
Code
Description
1-Order
3110
1-On/Off
2-Pompe
3-Reset Al.
4-Resume
5-Test
2-Clock
3120
1-Hour
2-Minute
3-Day
4-Month
5-Year
6-Win/Sum
1-Time
3210
1-Start Uno
3-Start z.A
5-Start z.B
7-Start z.C
2-
3220
1-Foot
Anticipation
2-Gradient
1-Water
3310
1-Sp Wat.1
Cool
2-Sp Wat.2
3-Sp Out.1
4-Sp Out.2
5-Reactiv.
2-Safety
3320
1-Wat. Low
Code
Unit
Min
Factory
3111
On/Off
~
Off
3112
Liste
0
0
3114
Yes/No
~
Off
3115
Yes/No
~
Off
3116
Liste
0
0
3121
H
0
~
3122
m
0
~
3123
~
1
~
3124
~
1
~
3125
~
2
~
3126
Yes/No
~
Yes
3211
h
0
24
3212
h
0
0
3213
h
0
24
3214
h
0
24
3221
°C
-10
10
3222
m/°C
0
0
3311
°C
5 / -10
7
3312
°C
5 / -10
7
3313
°C
-10
22
3314
°C
-10
30
3315
%/°C
1
5
3321
°C
3 / -10
5 / -10
CL50-CHILLERS/IOM/0105-E
Max
Comments
*[On / Off] Unit
~
pump operation mode set up (see Pump operation
6
description page 11 – IOM Climatic 50)
*[Reset] Discharges the safety measures of the
unit
~
*[Override] Cancel any override action set with
the DC50
~
3
Lennox set point
*[Clock] Clock setting "Hour"
23
*[Clock] Clock setting "minute''
59
*[Clock] Clock setting "Day"
31
*[Clock] Clock setting "Month"
12
*[Clock] Clock setting "Year"
99
*[Clock] automatic switch summer time / winter
time
~
*[Zone Setting] Starting time "Hour" for
"Unocupied" zone – set 6.3 to get 6h30mn –
modulo 10mn
24
*[Zone Setting] Starting time for "Zone A" – set
6.3 to get 6h30mn – modulo 10mn
24
*[Zone Setting] Starting time for "Zone B" – set
6.3 to get 6h30mn – modulo 10mn
24
*[Zone Setting] Starting time for "Zone C" – set
6.3 to get 6h30mn – modulo 10mn
24
*[Anticipation Function] Bottom of the slope in °C.
Limit of activation of the function. This allows an
anticipated startup in the morning depending on
the outdoor temperature. Only for the "Zone-A"
20
*[Anticipation Function] Slope in "Minutes of
anticipation per degrees".
100
*[Water SP]
Outlet chilled water temperature set point
(see page 11 – IOM Climatic 50) – minimum with
17
Glycol according to %
*[Water SP]
Outlet chilled water temperature set point
(see page 11 – IOM Climatic 50) – minimum with
17
Glycol according to %
*[Water SP]
Ambiant air temperature set point (see
50
page 13 – IOM Climatic 50)
*[Water SP]
Ambiant air temperature set point (see
50
page 13 – IOM Climatic 50)
*[Capacity Factor]
50
Reactivity factor for cooling mode
*[Safety limit]
Chilled water outlet temperature limit –
12
minimum with Glycol according to %
70
70