Fans Circuit Breakers Open - Lennox Climatic 50 User Manual

Hide thumbs Also See for Climatic 50:
Table of Contents

Advertisement

FAN(S) CIRCUIT BREAKER(S) OPEN
Description
One or more thermal magnetic trip circuit breaker protecting the condenser fans are tripped
Ecologic unit
Fault code 90
Ecomax unit circuit 1
Ecomax unit circuit 2
Ecomax unit circuit 3
Ecomax unit circuit 4
Reset
The fault is cleared automatically as soon as the fans circuit breakers are closed
Possible causes
Wrong wiring or tightening of the connections.
Wrong setting on the circuit breaker
CLIMATIC 50 user manual – chillers ranges
90, 92, 93, 94, 95
Fault Code:
code 92
code 93
code 94
code 95
Solving the problem
Control all connections
Set circuit breaker according with compressor
normal running current
CL50-CHILLERS/IOM/0105-E
FAULT CODES
36
36

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents