Thermo Pride OME-72D36 Installation And Service Manual page 39

Oil-fired furnace down flow & direct vent (sealed combustion)
Hide thumbs Also See for OME-72D36:
Table of Contents

Advertisement

All installations and services must be performed by qualified service personnel.
After fuel valve opens,
does the burner ignite?
Yes
Does the burner stay
lit past proof of flame
check?
Yes
Does the fan timer
energize the circulating
air blower after the 56
second time delay?
Yes
No
Is oil present in
the fuel line at the valve?
Are the ignition electrodes
positioned correctly?
Check for blocked or severely
worn burner nozzle. Clean
or replace as required.
Is the oil tank full of fuel? Is the
No
fuel clean without contaminates?
Is the fuel filter dirty?
Check settings on fan
timer against those
on connection
No
diagram. Is blower
still inoperable
after time delay
with fan timer
set correctly?
No
Yes
No
Yes
Yes
No
Measure voltage
on the circulating
Yes
air blower terminals.
Is it 120 VAC?
Yes
Does blower wheel
spin freely?
Yes
Is blower motor
capacitor functioning
properly?
Yes
Replace motor
37
Check the fuel supply.
Open all manual shutoff
valves serving the unit.
Purge any air in the
fuel line.
Reposition to
correct location.
Add or replace fuel and fuel
filter. Also, check cad cell
for proper operation.
Check wiring to
blower. If okay,
No
set fan selector
switch to manual.
If fan operates,
replace fan timer.
Check for blower wheel
No
rubing against housing
or motor shaft spinning
freely. Adjust or replace
as necessary.
No
Replace blower
motor capacitor.

Hide quick links:

Advertisement

Table of Contents