Hydronic piping
Figure 6-4 Pressure Drop vs. Flow
15 ft
14 ft
13 ft
12 ft
11 ft
10 ft
9 ft
8 ft
7 ft
6 ft
5 ft
4 ft
3 ft
2 ft
1 ft
0 ft
Table 6B Sizing Information for Temperature Rise Applications_20°F, 30°F, 40°F, 60°F and 80°F
MINIMUM
Model
PIPE
GPM
SIZE
400
2"
39
500
2"
49
600
2"
59
725
2 1/2"
71
850
2 1/2"
83
(continued)
HEX Pressure Drop
(Full Flow Application)
FTX725-850
TEMPERATURE RISE APPLICATIONS
20°F
30°F
FT/HD
GPM
FT/HD
3.5
26
4.8
33
4.4
39
4.9
47
5.7
55
FTX400-600
FTX400-600
Flow Rate
40°F
GPM
FT/HD
2.8
20
2.5
3.4
24
2.9
3.2
29
2.8
3.5
35
3.0
3.9
41
3.3
Installation & Operation Manual
15 ft
14 ft
FTX725 - 850
13 ft
12 ft
11 ft
10 ft
9 ft
8 ft
7 ft
6 ft
5 ft
4 ft
3 ft
2 ft
1 ft
0 ft
60°F
GPM
FT/HD
GPM
13
2.4
10
16
2.5
12
20
2.5
15
24
2.7
18
28
2.8
21
80°F
FT/HD
2.3
2.4
2.3
2.6
2.6
41