Optional Room Air - Lochinvar FTxl 400 Installation & Operation Manual

Hide thumbs Also See for FTxl 400:
Table of Contents

Advertisement

3
General venting
The PVC, CPVC, or ABS air inlet pipe should be cleaned and
sealed with the pipe manufacturer's recommended solvents
and standard commercial pipe cement for the material used.
The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe
should use a silicone sealant to ensure a proper seal at the
appliance connection and the air inlet cap connection. Dryer
vent or fl ex duct should use a screw type clamp to seal the vent
to the appliance air inlet and the air inlet cap. Proper sealing
of the air inlet pipe ensures that combustion air will be free of
contaminants and supplied in proper volume.
Follow the polypropylene manufacturer's instructions when
using polypropylene material as an inlet pipe.
When a sidewall or vertical rooftop combustion air supply
system is disconnected for any reason, the air inlet pipe must
be resealed to ensure that combustion air will be free of
contaminants and supplied in proper volume.
Failure to properly seal all joints and seams
DANGER
as required in the air inlet piping may
result in fl ue gas recirculation, spillage
of fl ue products and carbon monoxide
emissions causing severe personal injury
or death.

Optional room air

Optional room air is intended for
NOTICE
commercial applications.
air piping to the outside is recommended
for residential applications.
Commercial applications utilizing the FTXL boiler may be
installed with a single pipe carrying the fl ue products to the
outside while using combustion air from the equipment
room. In order to use the room air venting option the
following conditions and considerations must be followed.
The unit MUST be installed with the appropriate
bird screen (Table 3C).
The equipment room MUST be provided with
properly sized openings to assure adequate
combustion air. Please refer to instructions provided
with the room air kit.
Using the room air kit makes the unit vulnerable to
combustion air contamination from within the
building.
Please review Section 1, Prevent
Combustion Air Contamination, to ensure proper
installation.
Vent system and terminations must comply with the
standard venting instructions set forth in this
manual.
There will be a noticeable increase in the
NOTICE
noise level during normal operation from
the inlet air opening.
(continued)
WARNING
Table 3C Optional Room Air Kit
Model
400 - 850
Air contamination
Pool and laundry products and common household and hobby
products often contain fl uorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of fl ue gas spillage or
boiler water leakage into the building.
Please read the information given in Table 1A, page 10,
listing contaminants and areas likely to contain them.
contaminating chemicals will be present near the location of the
boiler combustion air inlet, have your installer pipe the boiler
Combustion
combustion air and vent to another location, per this manual.
WARNING
WARNING
Installation & Operation Manual
When utilizing the single pipe method,
provisions for combustion and ventilation
air must be in accordance with Air for
Combustion and Ventilation, of the latest
edition of the National Fuel Gas Code,
ANSI Z223.1, in Canada, the latest edition
of CGA Standard B149 Installation
Code for Gas Burning Appliances and
Equipment, or applicable provisions of
the local building codes.
Description
Room Air Kit
If the boiler combustion air inlet is located in
a laundry room or pool facility, for example,
these areas will always contain hazardous
contaminants.
To prevent the potential of severe personal
injury or death, check for areas and products
listed in Table 1A, page 10 before installing
the boiler or air inlet piping.
If contaminants are found, you MUST:
• Remove contaminants permanently.
—OR—
• Relocate air inlet and vent terminations
to other areas.
Kit Number
KIT30053
If
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ftxl 725Ftxl 500Ftxl 600

Table of Contents