General venting

Install vent and combustion air piping

The FTXL boiler must be vented and
DANGER
supplied with combustion and ventilation
air as described in this section. Ensure the
vent and air piping and the combustion
air supply comply with these instructions
regarding vent system, air system, and
combustion air quality. See also Section 1
of this manual.
Inspect fi nished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.
Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.
This appliance requires a special venting
WARNING
system. Use only approved stainless steel,
PVC, CPVC or polypropylene pipe and
fi ttings listed in Tables 3E, 3F, and 3H for
vent pipe, and fi ttings. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
DO NOT mix components from different
WARNING
systems.
causing leakage of fl ue products into the
living space. Mixing of venting materials
will void the warranty and certifi cation of
the appliance.
Installation must comply with local
NOTICE
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.
For closet and alcove installations, CPVC,
WARNING
polypropylene or stainless steel material
MUST BE used in a closet/alcove structure.
Failure to follow this warning could result
in fi re, personal injury, or death.
Improper installation of venting systems
CAUTION
may result in injury or death.
Follow the instructions in Section 1, page
NOTICE
11 of this manual when removing a boiler
from an existing vent system.
WARNING Do not connect any other appliance to
the vent pipe or multiple boilers to a
common vent pipe. Failure to comply
could result in severe personal injury,
death, or substantial property damage.
(continued)
The vent system could fail,
Installation & Operation Manual
The FTXL boiler vent and air piping can be installed through
the roof or through a sidewall. Follow the procedures in this
manual for the method chosen. Refer to the information in
this manual to determine acceptable vent and air piping length.
You may use any of the vent/air piping methods covered in this
manual. Do not attempt to install the FTXL boiler using any
other means.
You must also install air piping from outside to the boiler
air intake adapter unless following the Optional Room Air
instructions on page 19 of this manual. The resultant installation
is direct vent (sealed combustion).
The FTXL is certifi ed as a Category II/IV boiler. All venting
systems used with this boiler must be suitable for Category IV
operation except for factory approved common vent systems
operating as allowed in the Common Venting Section on page
20.
Air intake/vent connections
1.
Combustion Air Intake Connector (FIG. 3-1) - Used to
provide combustion air directly to the unit from outdoors. A
fi tting is provided on the unit for fi nal connection.
Combustion air piping must be supported per guidelines
listed in the National Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
2.
Vent Connector (FIG.'s 3-2 thru 3-7) - Used to provide a
passageway for conveying combustion gases to the
outside. A transition fi tting is provided on the unit for
fi nal connection. Vent piping must be supported per the
National Building Code, Section 305, Table 305.4 or as
local codes dictate.
Figure 3-1 Near Boiler Air Piping
17