Dr180 Blower Performance - 15 Ton High Static Drive (Gas Heat) - York SUNLINE MagnaDRY DR180C/E00 Technical Manual

Gas/electric single package
Table of Contents

Advertisement

036-21539-003-B-0305
TABLE 22: DR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT)
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP
0.2 7871 1145 6.22
7.65 7610 1106 5.69 7.00 7248 1070 5.04 6.20
0.4 7592 1143 6.00
7.38 7329 1103 5.41 6.66 6953 1069 4.76 5.86
0.6 7340 1147 5.72
7.04 7018 1108 5.16 6.35 6656 1071 4.51 5.55
0.8 7065 1147 5.44
6.69 6704 1109 4.87 5.99
1.0 6767 1148 5.14
6.32 6400 1110 4.55 5.59 6099 1073 4.04 4.84 5833 1034 3.58 4.30 5424 995 3.04 3.65 5041 956 2.63 3.16 4595 917 2.34 2.81
1.2 6451 1149 4.85
5.96 6079 1111 4.31 5.30 5749 1075 3.73 4.47 5473 1036 3.32 3.99 4989 997 2.84 3.41 4592 956 2.42 2.91
1.4 6127 1152 4.56
5.61 5719 1113 3.98 4.77 5392 1076 3.52 4.23 5063 1037 3.03 3.64 4525 997 2.55 3.06
1.6 5707 1153 4.24
5.21 5348 1115 3.71 4.46 4974 1077 3.22 3.86 4577 1038 2.74 3.29
1.8 5318 1155 3.98
4.78 4931 1116 3.41 4.10 4493 1078 2.83 3.40
2.0 4886 1156 3.56
4.27 4430 1118 3.18 3.81
0 turns
Chart shading corresponds to minimum motor horsepower requirements as defined below.
7.5 HP motor
8000
0 Turns
1 Turn
7500
2 Turns
3 Turns
7000
4 Turns
6500
5 Turns
6 Turns
6000
5500
5000
4500
0.0
0.2
Unitary Products Group
15 Ton High Static Drive Blower Performance (Horizontal Discharge)
6398
1072 4.26 5.24
1 turn
2 turns
5 HP motor
15-ton High Static Drive
VP60 & BK90
0.4
0.6
0.8
External Static ("WC)
7081
1032 4.46 5.49 6797 993 4.12 5.07 6442 953 3.66 4.39 6146 914 3.24 3.89
6769
1033 4.26 5.24 6478 993 3.86 4.63 6095 954 3.37 4.04 5805 915 2.99 3.58
6446
1033 3.99 4.79 6118 993 3.58 4.30
6175
1034 3.89 4.67 5758 994 3.35 4.02 5464 955 2.94 3.53 5050 916 2.50 3.00
3 turns
4 turns
1.0
1.2
1.4
5795
955 3.13 3.76 5402 914 2.81 3.37
5 turns
6 turns
1.6
1.8
2.0
39