Input Specifications - HP T2200 XR User Manual

Uninterruptible power system
Hide thumbs Also See for T2200 XR:
Table of Contents

Advertisement

Specifications

Input Specifications

Table C-2: Input Specifications
UPS Model
T2200 XR NA
T2200 XR JPN
T2200 XR H NA
T2200h XR H INT'L
Note:
Before connecting devices, verify that the UPS will not overload by checking that the rating
of the devices does not exceed the capacity of the UPS. Evenly distribute connected devices
throughout all load segments. Do not exceed the rating of individual receptacles. Connect
devices according to shutdown preference.
After checking that the UPS will not overload, connect the power cords from the devices to
the appropriate output receptacles of the UPS.
WARNING: To prevent risk of personal injury from electric shock, the
UPS T2200 XR H NA and T2200 XR H INT'L models are not suitable for installation
where the total earth (ground) conductor leakage current for all connected devices
exceeds 3.5 mA.
C-2
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Utility
Voltage
Frequency
(Hz)
Voltage (VAC)
50/60
50/60
50/60
50/60
120 on battery
1
110 on battery
2
220 on battery
3
HP Uninterruptible Power System T2200 XR Models User Guide
Default
Available
Settings
Settings
Nominal
Utility Voltage
(VAC)
120
110, 120, 127
2
100
100
3
208
208
230
220, 230, 240
Power Cord Supplied
1
Non-detachable
power cord with
NEMA 5-20 plug
Non-detachable
power cord with
NEMA L5-30 plug
IEC-320-C14 input
power receptacle
IEC-320-C14 input
power receptacle

Hide quick links: