INSTALLING iMOPS-150
Color Kinetics
®
iMOPS-150 is specially
designed to supply power and data to
iColor™ Cove lighting fixtures.
This fixture should be installed by a qualified
electrician in accordance with NEC and rele-
vant local codes for power supplies with
Class 2 outputs.
WARNING: iMOPS-150 is rated for instal-
lation in environments where the temperature
does not exceed 104ºF (40ºC). To ensure
product performance, a volume of 8 cubic
feet of air is required around the unit. Do not
obstruct the vent holes on the unit's cover.
This power supply is not suited for outdoor
locations and must be shielded from water
spray.
Unpacking
• Lift the power supply out of the housing,
and remove the packing material from the
cover and power supply. (See Fig. 1.)
MODEL # PWR-iMOPS-150-01
© 2000 Color Kinetics Incorporated. Color Kinetics is a
registered trademark and Chromacore, ColorBlast,
ColorPlay, iColor, iPlayer and Smartjuice are trade-
marks of Color Kinetics Incorporated.
MAN - 0012 Rev 03
Fig. 1
Cover
Screws
(#6-32)
Housing
Power
supply
Mounting the iMOPS Housing
• Select the location to mount the housing,
keeping in mind that the maximum cable
run from iMOPS-150 to any iColor Cove
fixture is 50 feet.
• Punch out the appropriate number of
pre-formed 3/4" conduit holes. At least 3
holes are recommended to separate the
following: incoming power (line voltage),
incoming data, and outgoing data and
power (DC voltage).
• Mount the housing to the wall using four
#6 dry wall screws. Mounting holes are
located at the bottom of the housing, one
at each corner.
Connecting iColor Cove
Fixtures to the Power Supply
There are two main output terminals on the
power supply, labeled OUT 1 and OUT 2.
Number of iColor Cove segments supported:
iColor Cove
6"
OUT 1
16
OUT 2
16
Total
32
WARNING: Make sure the power supply is
off before connecting or disconnecting fix-
tures. Otherwise, damage to the fixture may
result.
• Connect the iColor Cove master cable to
the green output terminals. (See Fig. 2.)
Fig. 2
Master cable
Red
Blue
Black
Recommended wiring schemes are shown in
Fig. 3a and 3b.
IMPORTANT: In any wiring configuration,
master cable runs must not exceed fifty feet
per output terminal.
Spare
Fig. 3a
fuses (4)
COVE
POWER SUPPLY
Place power supply halfway along cove and run
master cables of equal lengths to each end of cove.
Fig. 3b
COVE
Place power supply at one end
of cove and run master cable to
POWER SUPPLY
closest end and midpoint of cove.
Connecting Data to the
Power Supply
• Connect the controller to the output termi-
nal labeled AUXILIARY. (See Fig 4.) This
terminal supplies power to the controller
and also receives data, which it sends to
each iColor Cove fixture.
Fig. 4.
Power out
To controller
Data in
12"
WARNING: The AUXILIARY terminal is
10
10
designed for use only with Color Kinetics
20
controllers, such as Synchronizer, Multi
Synchronizer, and iPlayer™. Do not use the
AUXILIARY terminal to power lights.
• Alternatively, you can connect the con-
troller to the DATA IN RJ45 port. In this
case, the controller must be powered by
another source.
• To send data to another iMOPS-150 or
other Color Kinetics product with direct
DMX input, connect an RJ45 cable
RED
BLU
between the LOOP OUT port of the send-
BLK
ing unit and the DATA IN port of the receiv-
ing unit. (See Fig. 5.)
Fig. 5
Auxiliary
OUT
IN
Data In
Loop Out
Data In Loop Out
To sending iMOPS
or controller
• Make sure a terminator is installed in the
LOOP OUT port of the last unit in the
chain. (See Fig. 6.) Single units should also
be terminated. (Data terminators are avail-
able from Color Kinetics.)
Fig. 6
Auxiliary
OUT
IN
Data In
Loop Out
Data In Loop Out
To sending iMOPS
or controller
Ground
GND
+24V DC
+24
Data +
D+
Data –
D-
Ground
GND
OUT 1
OUT 2
Repeater Out
F1
F2
To receiving iMOPS
OUT 1
OUT 2
Repeater Out
F1
F2
Terminator

Advertisement

loading
Need help?

Need help?

Do you have a question about the i mops- 150 and is the answer not in the manual?

Questions and answers

Summary of Contents for Color Kinetics i mops- 150

  • Page 1 MODEL # PWR-iMOPS-150-01 ing unit and the DATA IN port of the receiv- Tel 888 Full RGB © 2000 Color Kinetics Incorporated. Color Kinetics is a ing unit. (See Fig. 5.) Tel 617 423 9999 registered trademark and Chromacore, ColorBlast,...
  • Page 2: Replacing Fuses

    (See Fig. 12.) If an — (Ground) • If Color Kinetics is unable to repair or replace the than 400 feet. Make sure a terminator is output terminal is not functioning, replace the particular product, refund the then current value of installed in the LOOP OUT port if the the product.