Protection Operation Outdoor Unit - Technibel MPAFIA0R5IAA Service Manual

Split system air conditioner
Table of Contents

Advertisement

5-10 Protection operations on outdoor unit
5-10.1 Overheating
During cooling operation as soon as the outdoor coil temperature (OCT) increases, compressor speed
is reduced in order to avoid heat exchanger overheating. System stops compressor operation when OCT
reaches 60 °C
5-10.2 Compressor discharge temperature
During operation, as soon as the discharge temperature increases, (CDT) compressor speed is reduced
in order to avoid overheating of the motor. Compressor is stopped when CDT reaches 110°C
5-10.3 Compressor power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system and
kept operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
5-10.4 Outdoor fan power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system and
kept operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
5-10.5 Compressor power-module overcurrent
Operation is automatically stopped in case of current driven to each motor phase greater than a value
depending on the power of the outdoor unit (9A for 12000btu and 11A for 18000btu)
5-10.6 Outdoor fan power-module overcurrent
In case of current driven to each motor phase greater than 300mA operation is automatically stopped
15