Temperatures Menu - Lochinvar HS 50 Series 100 Instruction Manual

Commercial electric water heater
Table of Contents

Advertisement

stAtE
The water heater is not in an active heating cycle. This usually indicates the temperature in the tank has reached
Standby
the Operating Set Point and the control system has terminated the heating cycle.
Heating
The control system is in the Heating Mode. At least one bank of heating elements has been energized.
The control system has detected/declared an Alert Condition. The controls system will continue heating operation.
Alert
However, a Qualified Service Agent should be contacted to check/service the water heater.
The control system has detected/declared a Fault Condition. The control system will discontinue heating operation
Fault
and "lock out." Power to the water heater must be cycled off and on to reset the control system. Note; cycling power
will not reset the control system until the condition that caused the fault has been corrected.
MEnus
Most commonly accessed menu. Operating Set Point, Differential settings, Tank Temperature and Tank Probe
Temperatures
Offset are located in this menu.
Current Operating State/Mode (heating/standby etc) and status (open/closed - on/off - yes/no) of monitored water
Heater Status
heater functions and components are displayed in this menu.
Economy Mode
Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied
Setup
or reduced demand periods.
The control system's CCB (Central Control Board) features on board SPDT (single pole double throw) relay contacts
Alarm Output
for building EMS (Energy Management System) notification of operational conditions such as Fault Conditions and
Setup
heating mode status. This menu features a list of user definable conditions for relay activation.
Temperature units (°F or °C), appearance (brightness contrast) and backlight delay user adjustable settings are
Display Settings
located in this menu.
Elapsed time of operation, total heating cycle time, heating cycle count, heating element bank(s) cycle count and
Heater Information
heating bank on time along with UIM and CCB software revisions can be viewed in this menu.
Current Fault/Alert
Displays any current Alert or Fault messages.
Retains 9 event history of Fault/Alert messages with time stamp. The Fault History is useful when dealing with intermittent
Fault History
operational problems or when the customer has reset the control system prior to a service agent's arrival.
Running total of all Fault and Alert Conditions that have occurred are displayed in this menu. Can help determine
Fault Occurrence
potential root cause(s) of related operational problems.
Restore Factory
This control system feature allows the user to restore control system user settings to their factory default settings.
Defaults
Alarm Output Setup and Display Settings menu items ARE NOT changed when factory defaults are restored.
Accessible by pressing the corresponding Operational Button from most menus and screen displays. This menu
Help Menu
provides access to instructions and explanations for user settings, Operating States, Status Icons, manufacturer's
web address, technical support phone number and service agent contact information.

tEMPErAturEs MEnu

operating set Point
User adjustable setting 90°F to 190°F range; factory default is
120°F. When the water temperature sensed by the control system
from the immersion Temperature Probe reaches the Operating Set
Point the control system will end the heating cycle. A call for heat
will be activated again when the water temperature drops below the
Operating Set Point minus the 1st Differential Setting.
Example: Operating Set Point is 120°F, the 1st Differential Setting is
2°F (factory default). A call for heat will be activated when the sensed
water temperature drops to 118°F.