Lochinvar HS 50 Series 100 Instruction Manual page 16

Commercial electric water heater
Table of Contents

Advertisement

ConVErsIon to sInGLE PhAsE
When the heater is shipped for connection to a three-phase electrical
service, it may be connected to a single-phase electrical service of
the same voltage by:
1. Disconnect blue wires and yellow wires from terminal L3.
2. Reconnect all blue wires to terminal L1 (with black wires).
3. Reconnect all yellow wires to terminal L2 (with red wires).
4. Connect incoming power to terminals L1 and L2.
wIrInG dIAGrAMs
nInE ELEMEnt - sInGLE And thrEE PhAsE
dIAGrAM 2.
16
ConVErsIon to thrEE PhAsE
When heater is shipped for connection to a single-phase electrical
service, it may be connected to a three-phase electrical service of
the same voltage by:
1. Disconnect blue wires from terminal L1.
2. Disconnect yellow wires from terminal L2.
3. Reconnect all blue wires and yellow wires to terminal L3.
4. Connect incoming power to terminals L1, L2, and L3.