K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
4.0

COMFORT ADJUSTMENTS

?? Outlet air is initially too warm or too cold - adjust the "FAN ON" setting.
?? Outlet air consistently too warm or too cold - change the blower motor speed to
give the specified air temperature rise (70 - 85°F).
?? Blower motor shuts off and the oil burner keeps going - the "FAN ON" setting is
set too low or the inlet air is below 50°F.
?? Outlet air gets too warm and burner shuts down - increase air by changing the
blower motor speed to give the specified temperature rise (70 - 85°F).
?? Outlet air is too warm or too cold at the end of the heating cycle after the burner
has turned off - adjust the "FAN OFF" time higher or lower.
5.0
REGULAR MAINTENANCE & CLEANING
Check complete operation at least once a year. In Canada see B139, Section 14,
Maintenance, for recommended servicing procedure.
accessed through breech access panel at front of unit. Replace stainless steel gas
baffles after cleaning. Cerafelt (1/4") gaskets may have to be replaced.
K4C Compact-multi
Heat exchanger ducts are