COOLING AIRFLOW REQUIREMENT (CFM)
600
0453__XA
376*
0704__XA
---
0905__XA
---
1155__XA
---
COOLING AIRFLOW REQUIREMENT (CFM)
600
0704__XA
---
0905__XA
---
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
0453__XA
376*
0704__XA
---
0905__XA
---
1155__XA
---
COOLING AIRFLOW REQUIREMENT (CFM)
600
800
0704__XA
---
0905__XA
---
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter area (sq. in)
[Based on 300 ft/min filter face velocity]
U
I
PRIGHT
NSTALLATIONS
Depending on the installation and/or customer preference, differing
filter arrangements can be applied. Filters can be installed in the
central return register or a side panel external filter rack kit (upflows).
As an alternative a media air filter or electronic air cleaner can be
used as the requested filter.
The following figure shows possible filter locations.
IO-243
UPFLOW
800
1000
1200
1400
1600
384
480
576
---
---
627*
627*
672
---
---
836*
836*
836*
---
---
940*
940*
940*
COUNTERFLOW
800
1000
1200
1400
1600
---
320*
320*
336
---
---
427*
427*
427*
UPFLOW
1000
1200
1400
1600
384
480
576
---
---
564*
564*
672
---
---
752*
752*
---
---
940*
940*
940*
COUNTERFLOW
1000
1200
1400
1600
---
641*
641*
672
---
---
854*
854*
854*
2000
---
---
CENTRAL
768
---
RETURN
GRILLE
SIDE RETURN
960
EXTERNAL FILTER
RACK KIT
(EITHER SIDE)
960
2000
384
---
Possible Upright Upflow
480
NOTE: Internal filter retention is not provided on this furnace. If an
internal installation is desired, an internal filter retention kit is avail-
able as an accessory. Please see your distributor for details.
H
ORIZONTAL
2000
Filters must be installed in either the central return register or in the
return air duct work.
---
---
XIV
XIV
. ST
. ST
XIV. ST
XIV
XIV
. ST
. STAR
768
Furnace must have a 115 VAC power supply properly connected
and grounded. Proper polarity must be maintained for correct op-
768
960
eration. In addition to the following start-up and adjustment items,
960
refer to further information in Section XVI, Operational Checks.
H
A
EAT
NTICIPATOR
The heat anticipator in the room thermostat must be correctly ad-
justed to obtain the proper number of cycles per hour and to prevent
2000
"overshooting" of the setting. Set the heat anticipator setting to 0.7
768
---
amps. Follow the thermostat manufacturer's instructions on how to
adjust the heat anticipator setting.
960
D
T
RAIN
RAP
The drain trap must be primed prior to furnace startup. To prime, fill
the drain trap with water. This ensures proper furnace drainage upon
startup and prohibits the possibility of flue gases escaping through
the drain system.
F
URNACE OPERATION
Purge gas lines of air prior to startup. Be sure not purge lines into an
enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water
solution, an electronic combustible gas detector, or other approved
method. Verify that all required kits (propane gas, high altitude, etc.)
have been appropriately installed.
F
S
URNACE
TARTUP
1. Close the manual gas shutoff valve external to the furnace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by hand.
5. Move the furnace gas valve manual control to the OFF
position.
27
FILTER
ACCESS
DOOR
RETURN
AIR FLOW
DUCT
FILTER
SUPPORT
BRACKET
KIT
Possible Upright Counterflow
Filter Locations
I
NSTALLATIONS
AR
AR
TUP PR
TUP PR
OCEDURE & AD
OCEDURE & AD
AR
ARTUP PR
TUP PROCEDURE & AD
TUP PR
OCEDURE & ADJUST
OCEDURE & AD
S
ETTING
P
RIMING
CENTRAL
RETURN
GRILLE
AIR FLOW
JUST
JUST
MENT
MENT
JUST
JUSTMENT
MENT
MENT
6/04