Carrier Ecologic 30GX080-265 Controls, Start-Up, Operation, Service, And Troubleshooting page 32

Ecologic air-cooled and fluid cooled chillers
Hide thumbs Also See for Ecologic 30GX080-265:
Table of Contents

Advertisement

Table 19 — Service Function and Subfunction Directory (cont)
SUBFUNCTION
3 Options Configuration 2 (cont)
4 Reset Configuration Table
KEYPAD ENTRY
DISPLAY
Ramp Load Select
x
Clock Control Select
x
Ice Configuration Select
x
OAT Sensor Select
x
Remote Alarm Select
x
Alarm Reset Select
x
Close Control Select
x
Deadband Multiplier
x.x
Current Unbalance Alarm
x
Voltage Unbalance Alarm
x
COOLING RESET TYPE
1
Degrees Reset at 20 mA
xx.x dF
COOLING RESET TYPE
2
Remote temp=No Reset
xx.x dF
Remote temp=Full Reset
xx.x dF
Degrees Reset
xx.x dF
COOLING RESET TYPE
3
CHW Delta T=No Reset
xx.x dF
CHW Delta T=Full Reset
xx.x dF
Degrees Reset
xx.x dF
COOLING RESET
Select/Enable Reset Type
x
HEATING RESET TYPE
1
Degrees Reset at 20 mA
xx.x dF
HEATING RESET TYPE
2
Remote temp=No Reset
xx.x dF
Remote temp=Full Reset
xx.x dF
Degrees Reset
xx.x dF
HEATING RESET TYPE
3
HTW Delta T=No Reset
xx.x dF
HTW Delta T=Full Reset
xx.x dF
Degrees Reset
xx.x dF
HEATING RESET
Select/Enable Reset Type
x
DEMAND LIMIT
Demand Limit at 20 mA
xxx.x%
0 = Disabled, 1 = Enabled (Default)
See page 8
0 = No clock control (Default)
1 = Local clock control
65 = CCN Clock Control
0 = Disabled (Default)
1 = Clock Control
2 = Demand Limit Control
0 = Disabled, 1 = Enabled
Default: 0
0 = Disabled, 1 = Enabled
Default: 0
0 = Not selected, 1 = Selected
(Default, allows use of LOR
switch to reset alarms)
0 = Disabled, 1 = Enabled
Default: 0. See page 7
Default: 1.0
Alarm at 10% imbalance; 0 = Disabled, 1 = Enabled
Default: 1
Alarm at 3% imbalance; 0 = Disabled, 1 = Enabled
Default: 1
See Demand Limit section, page 39
Default: 0
Default: 20
Default: 125
Default: 0
Default: 15
Default: 0
Default: 0
0 = No Reset (Default) , 1 = 4-20 mA Reset,
2 = External Reset, 3 = Return Fluid Reset
CURRENTLY NOT SUPPORTED
Default: 0
CURRENTLY NOT SUPPORTED
Default: 125
Default: 20
Default: 0
CURRENTLY NOT SUPPORTED
Default: 15
Default: 0
Default: 0
0 = No Reset (Default), 1 = 4-20 mA reset,
2 = External reset, 3 = Return Fluid reset
See Demand Limit section, page 39
Enter 0-100, Default: 0%