Suitable Fuels; Data Plate; Tools, Materials And Auxiliary Equipment; Product Description - Bosch Uni Cindens 6000F Installation Instructions Manual

Floor standing condensing boiler output range 800 - 1200 kw
Table of Contents

Advertisement

2.7

Suitable fuels

The combustion of biogas is not permitted.
Permissible fuels
• Natural gas from the public gas supply in accordance with national
regulations with a total sulphur content < 50 mg/m
• LPG in accordance with national regulations with a content of
elementary sulphur < 1.5 ppm and volatile sulphur < 50 ppm.
The boiler must only be operated with the specified fuels. Only burners
that are suitable for the specified fuels may be used.
Observe the manufacturer's burner selection list and the burner
manufacturer's instructions.
2.8

Data plate

If you contact the manufacturer with any questions about
this product, always provide the details on the data
plate. These details enable us to assist you specifically
and quickly.
The data plate is fitted to the back of the boiler casing.
There you will find information such as the serial number, output and
approval details.
2.9

Tools, materials and auxiliary equipment

For the installation and maintenance of the boiler, standard tools are
required, as used for heating, gas, water and electrical installations.

2.10 Product description

The Uni Condens 6000F is a floor standing condensing boiler with a slim,
compact design and a small footprint thanks to the combustion chamber
being located at the top and the condensation heating surface being
located at the bottom. In the following, it is referred to as the Uni
Condens 6000F or the boiler.
The Uni Condens 6000F has two thermohydraulically separated return
connections for the high and low temperature circuits.
For the type-tested boiler sizes with internal condensing heat exchanger
and CE designation, the components that come into contact with hot gas
and condensate are made of stainless steel.
Equip the Uni Condens 6000F with a suitable burner.
Optional accessories can be found in the general catalogue.
NOTICE: System damage through the use of an
incorrect burner.
B Only use burners that meet the
technical requirements of the boiler
(
chapter 2.11, page 7).
The following are the main components of the Uni Condens 6000F are
(
Fig. 1, page 6):
• Boiler body [1] in conjunction with a burner
The boiler block transfers the heat produced by the burner to the
heating water.
• Thermally insulating casing
The boiler jacket and thermal insulation reduce energy losses.
• Control unit [8] (accessory)
The control unit monitors and controls all electrical boiler
components.
Uni Condens 6000F
3
.
About the boiler | 5
6 720 803 637 (2012/03)