INSTALLATION, OPERATION & MAINTENANCE MANUAL SINGLE PACKAGED ROOF TOP AIR CONDITIONERS 'PS' SERIES MODELS: PS036 - PS360 Part Number: 800-213-04...
INDEX Contents Page General Model decoding ..............................2 General statement ..............................3 Warranty ................................. 3 Safety issues ................................3 Inspection for damage ............................3 Installation instructions General ................................... 4 Location of unit ............................... 4 Service clearance ..............................5 Rigging instructions ..............................5 Condensate drain connection ..........................
INSPECTION FOR DAMAGE The unit should be carefully inspected visually for any sign of physical damage due to mishandling. Whenever a damage is detected, please indicate it on the corresponding delivery note before you sign it and inform your nearest “Zamil” office.
INSTALLATION INSTRUCTIONS GENERAL These units are shipped completely assembled, charged, and wired. They do not require any field installation of refrigerant tubing. Units require external power, thermostat wiring, condensate drain piping and ducting as applicable. Size of unit for an installation should be based on a heat gain calculation made according to applicable standards. Units must also be installed in accordance with regulations of the "National Fire Protection Association"...
SERVICE CLEARANCE MODELS: PS036 - PS120 MODELS: PS180 - PS360 NOTE: Only two condenser fans for models PS180 - PS240. NOTE: All dimensions are in cm. MODEL DIMENSIONS MODEL DIMENSIONS NUMBER NUMBER PS036 PS180 PS048 PS215 PS240 PS060 PS075 PS300...
For selecting cable size, refer to wire ampacity table at different MCA (Minimum Circuit Amps) provided in unit electrical data, which is listed as a guideline. • Wiring connection to the unit must have suitable insulation of a minimum temperature of 90 UNIT WEIGHT & WEIGHT DISTRIBUTION WEIGHT (Kg.) MODEL NUMBER PS036 PS048 PS060 PS075 PS090 PS100 PS120 PS180...
Page 9
UNIT DIMENSIONS PS090 - PS120 TOP VIEW SIDE VIEW FRONT VIEW SIDE VIEW NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides.
Page 10
UNIT DIMENSIONS PS180 TOP VIEW SIDE VIEW FRONT VIEW SIDE VIEW NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides.
Page 11
UNIT DIMENSIONS PS215 - PS240 TOP VIEW SIDE VIEW SIDE VIEW FRONT VIEW NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides.
Page 12
UNIT DIMENSIONS PS300 - PS360 TOP VIEW FRONT VIEW SIDE VIEW SIDE VIEW NOTE: 1. All dimensions are in mm (dimensions in brackets are in inches). 2. Service clearance should be 1200mm (4 feet) on all sides.
OPERATION INSTRUCTIONS START-UP, INSPECTION & CHECK LIST After the installation is completed in all respect, the following points should be covered before the system is switched on for operation. Check unit location as per installation instructions. Make sure all electrical fasteners/connections are tight and clean. All controls are set according to manufacturer's instructions (low &...
ELECTRICAL DATA MODELS: PS036 & PS048 MODEL NUMBER DESCRIPTION PS036 PS048 COMPR- COMPR- VOLTAGE ELECTRIC ELECTRIC ESSOR ESSOR POWER RANGE HEATER HEATER (each) MOCP MOCP (each) (each) SUPPLY (V-Ph-Hz) Min. Max. RLA LRA HP FLA Nom. kW RLA LRA HP FLA Nom. kW –...
Page 15
ELECTRICAL DATA MODELS: PS090 & PS100 MODEL NUMBER DESCRIPTION PS090 PS100 COMPR- COMPR- VOLTAGE ELECTRIC ELECTRIC ESSOR ESSOR POWER RANGE HEATER HEATER (each) MOCP MOCP (each) (each) SUPPLY (V-Ph-Hz) Min. Max. RLA LRA HP FLA Nom. kW RLA LRA HP FLA Nom. kW –...
Page 16
ELECTRICAL DATA MODELS: PS120 & PS180 MODEL NUMBER DESCRIPTION PS120 PS180 COMPR- COMPR- VOLTAGE ELECTRIC ELECTRIC ESSOR ESSOR POWER RANGE HEATER HEATER (each) MOCP MOCP (each) (each) SUPPLY (V-Ph-Hz) Min. Max. RLA LRA HP FLA Nom. kW RLA LRA HP FLA Nom. kW –...
Page 17
ELECTRICAL DATA MODELS: PS215 & PS240 MODEL NUMBER DESCRIPTION PS215 PS240 COMPR- COMPR- VOLTAGE ELECTRIC ELECTRIC ESSOR ESSOR POWER RANGE HEATER HEATER (each) MOCP MOCP (each) (each) SUPPLY (V-Ph-Hz) Min. Max. RLA LRA HP FLA Nom. kW RLA LRA HP FLA Nom. kW –...
Page 18
ELECTRICAL DATA MODELS: PS300 & PS360 MODEL NUMBER DESCRIPTION PS300 PS360 COMPR- COMPR- VOLTAGE ELECTRIC ELECTRIC ESSOR ESSOR POWER RANGE HEATER HEATER (each) MOCP MOCP (each) (each) SUPPLY (V-Ph-Hz) Min. Max. RLA LRA HP FLA Nom. kW RLA LRA HP FLA Nom. kW –...
Performex-1 CONTROLLER : OPERATION & FUNCTIONS The Zamil Packaged units are provided with technologically advanced new Performex Controller Microprocessor Based Electronic Control Board, incorporating the following benefits and features: - COMPLETE UNIT CONTROL: Provides complete unit control for heating and cooling application whether single stage or two stage utilizing the input from sensor that measure temperatures during unit operation.
7. LEAD/LAG OPERATION: Whenever a compressor needs to be on, the controller will turn on the compressor with the shorter accumulated run time provided its 3 minutes minimum off time has lapsed. Otherwise the other compressor will on first. Similarly, the compressor with the longer accumulated run time will be the first one to be cut off. This is to load the compressors evenly over long run period.
MAINTENANCE INSTRUCTIONS AIRFLOW ADJUSTMENT (Applicable for PS075 - PS360 only) The airflow could be adjusted by adjusting pulleys of blower motor or belt tension with proper mounting and alignment of the pulleys: • Refer to fan performance tables in the catalog for selecting applicable airflow, RPM and brake horse power at specified static pressure.
BELT TENSION TESTING PROCEDURE BELT SPAN D EFLEC TI O N = FO R C E SC ALE SM ALL " 0" R I N G BELT SPAN SPAN SC ALE LAR G E " 0" R I N G BELT TENSION CHECKER MEASURE THE BELT DEFLECTION FORCE BELTS...
PREVENTIVE MAINTENANCE SCHEDULE CAUTION: Disconnect power supply and allow all rotating parts to stop before servicing the unit. FREQUENCY OF MAINTENANCE, MONTHS (FIRST 4 YEARS) I T E M Clean air filter (Aluminum)* Pressure wash condenser & cooling coil as required Check blower belt, tension, wear tear/replace if required Check alignment of pulleys Clean drain pan, drain pipe...
TROUBLE SHOOTING CHART SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE Thermostat shows no display 1. Power off/Blown fuse 1. Check the power. Switch ON the circuit breaker. Replace fuse if it blown. 2. Faulty field wiring 2. Check wiring against diagram. 3.
Page 25
TROUBLE SHOOTING CHART SYMPTOM CAUSES CHECK & CORRECTIVE MEASURE 1. Low suction pressure 1. Verify the reason & correct it (refer to symptom Unit works continuously, no sufficient for "low suction pressure"). cooling 2. High discharge pressure 2. Verify the reason and adjust the freon, if required.(refer to symptom for "high discharge pressure").
Page 32
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS090 - PS120 (Dual compressor units) (POWER SUPPLY: 208/230V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 33
SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,...
Page 34
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS090 - PS120 (Dual compressor units) (POWER SUPPLY: 380V - 3Ph - 60Hz) TO HVTB TO NTB NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 35
SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,...
Page 36
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS090 - PS120 (Dual compressor units) (POWER SUPPLY: 460V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 37
SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,...
Page 38
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS180 - PS240 (Dual compressor units) (POWER SUPPLY: 208/230V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 39
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN.
Page 40
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS180 - PS240 (Dual compressor units) (POWER SUPPLY: 380V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 41
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN.
Page 42
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS180 - PS240 (Dual compressor units) (POWER SUPPLY: 460V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 43
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN.
Page 44
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS300 - PS360 (Dual compressor units) (POWER SUPPLY: 208/230V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 45
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN.
Page 46
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS300 - PS360 (Dual compressor units) (POWER SUPPLY: 380V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 47
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN.
Page 48
TYPICAL SCHEMATIC WIRING DIAGRAM MODELS : PS300 - PS360 (Dual compressor units) (POWER SUPPLY: 460V - 3Ph - 60Hz) NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items. 2. Refer to unit control box (inside panel) for exact wiring diagram.
Page 49
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RE- SULT IN COMPRESSOR DAMAGE. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL. 6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVER- LOAD. 7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS SHOWN.