Lennox XP14 SERIES Unit Information page 9

Xp14 series high efficiency residential split system heat pump unit
Table of Contents

Advertisement

DS2
DS1
Green
Red
Condition/Code
OFF
OFF
Power problem
Simultaneous
Normal operation
SLOW Flash
Alternating
5−minute anti−short cycle
SLOW Flash
delay
Simultaneous
Ambient Sensor Problem
FAST Flash
Alternating
Coil Sensor Problem
FAST Flash
ON
ON
Circuit Board Failure
FAULT & LOCKOUT CODES (Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT)
OFF
SLOW
Low Pressure Fault
Flash
OFF
ON
Low Pressure LOCKOUT
SLOW
OFF
High Pressure Fault
Flash
ON
OFF
High Pressure LOCKOUT
TABLE 2
Diagnostic Fault Code
Possible Cause(s)
No power (24V) to control termi-
nals R & C or board failure.
Unit operating normally or in
standby mode.
Initial power up, safety trip, end of
room thermostat demand.
Sensor being detected open or shorted or out of temperature range. Control will
revert to time/temperature defrost operation. (System will still heat or cool).
Sensor being detected open or shorted or out of temperature range. Control will not
perform demand or time/temperature defrost operation. (System will still heat or
cool).
Indicates that control has internal component failure. Cycle 24 volt power to control.
If code does not clear, replace control.
1
Restricted air flow over indoor or
outdoor coil.
2
Improper refrigerant charge in
Improper refrigerant charge in
system.
3
Improper metering device
installed or incorrect operation
installed or incorrect operation
of metering device.
4
Incorrect or improper sensor
location or connection to sys
location or connection to sys-
tem.
Page 9
Solution
1
Check control transformer power (24V).
2
If power is available to control and LED(s) do
not light, replace board.
None required.
None required (Jumper TEST pins to override)
1
Remove any blockages or restrictions from
coils and/or fans. Check indoor and outdoor
fan motor for proper current draws.
fan motor for proper current draws.
2
2
Check system charge using approach & sub-
cooling temperatures.
3
3
Check system operating pressures and
Check system operating pressures and
compare to unit charging charts.
4
Make sure all pressure switches and sensors
have secure connections to system to prevent
have secure connections to system to prevent
refrigerant leaks or errors in pressure and
temperature measurements.