TABLE 8
HFC−410A Temp. (°F) − Pressure (Psig)
°F
Psig
°F
Psig
32
100.8
63
178.5
33
102.9
64
181.6
34
105.0
65
184.3
35
107.1
66
187.7
36
109.2
67
190.9
37
111.4
68
194.1
38
113.6
69
197.3
39
115.8
70
200.6
40
118.0
71
203.9
41
120.3
72
207.2
42
122.6
73
210.6
43
125.0
74
214.0
44
127.3
75
217.4
45
129.7
76
220.9
46
132.2
77
224.4
47
134.6
78
228.0
48
137.1
79
231.6
49
139.6
80
235.3
50
142.2
81
239.0
51
144.8
82
242.7
52
147.4
83
246.5
53
150.1
84
250.3
54
152.8
85
254.1
55
155.5
86
258.0
56
158.2
87
262.0
57
161.0
88
266.0
58
163.9
89
270.0
59
166.7
90
274.1
60
169.6
91
278.2
61
172.6
92
282.3
62
175.4
93
286.5
°F
Psig
°F
Psig
94
290.8
125
445.9
95
295.1
126
451.8
96
299.4
127
457.6
97
303.8
128
463.5
98
308.2
129
469.5
99
312.7
130
475.6
100
317.2
131
481.6
101
321.8
132
487.8
102
326.4
133
494.0
103
331.0
134
500.2
104
335.7
135
506.5
105
340.5
136
512.9
106
345.3
137
519.3
107
350.1
138
525.8
108
355.0
139
532.4
109
360.0
140
539.0
110
365.0
141
545.6
111
370.0
142
552.3
112
375.1
143
559.1
113
380.2
144
565.9
114
385.4
145
572.8
115
390.7
146
579.8
116
396.0
147
586.8
117
401.3
148
593.8
118
406.7
149
601.0
119
412.2
150
608.1
120
417.7
151
615.4
121
423.2
152
622.7
122
428.8
153
630.1
123
434.5
154
637.5
124
440.2
155
645.0
V − SERVICE AND RECOVERY
WARNING
Polyol ester (POE) oils used with HFC−410A refrig-
erant absorb moisture very quickly. It is very impor-
tant that the refrigerant system be kept closed as
much as possible. DO NOT remove line set caps or
service valve stub caps until you are ready to make
connections.
IMPORTANT
Use recovery machine rated for HFC−410A refriger-
ant.
If the XP14 system must be opened for any kind of service,
such as compressor or drier replacement, you must take
extra precautions to prevent moisture from entering the
system. The following steps will help to minimize the
amount of moisture that enters the system during recovery
of HFC−410A.
1 − Use a regulator−equipped nitrogen cylinder to break
the system vacuum. Do not exceed 5 psi. The dry nitro-
gen will fill the system, and will help purge any mois-
ture.
2 − Remove the faulty component and quickly seal the sys-
tem (using tape or some other means) to prevent addi-
tional moisture from entering the system.
3 − Do not remove the tape until you are ready to install
new component. Quickly install the replacement com-
ponent.
4 − Evacuate the system to remove any moisture and other
non−condensables.
The XP14 system MUST be checked for moisture any
time the sealed system is opened.
Any moisture not absorbed by the polyol ester oil can be re-
moved by triple evacuation. Moisture that has been ab-
sorbed by the compressor oil can be removed by replacing
the drier.
IMPORTANT
Evacuation of system only will not remove mois-
ture from oil. Drier must be replaced to eliminate
moisture from POE oil.
Page 20