Trane AquaStream CGWN 205 Installation Operation & Maintenance page 29

Indoor liquid chiller with integrated hydraulic module
Hide thumbs Also See for AquaStream CGWN 205:
Table of Contents

Advertisement

Table 12 - Recommended discharge line diameters for horizontal risers (Circuit 1)
Unit size
-12
CCUN
205
CCUN
206
CCUN
207
CCUN
208
CCUN
209
CCUN
210
CCUN
211
CCUN
212
CCUN
213
CCUN
214
CCUN
215
Table 13 - Recommended discharge line diameters for horizontal risers (Circuit 2)
Unit size
-12
CCUN
205
CCUN
206
CCUN
207
CCUN
208
CCUN
209
CCUN
210
CCUN
211
CCUN
212
CCUN
213
CCUN
214
CCUN
215
CG-SVX06D-E4
Installation
Required discharge pipe diameter - Circuit 1
-10
-8
-6
-4
7/8"
7/8"
7/8"
1"1/8
1"1/8
1"1/8
1"1/8
1"5/8
1"5/8
1"5/8
1"5/8
Required discharge pipe diameter - Circuit 2
-10
-8
-6
-4
7/8"
7/8"
7/8"
1"1/8
1"1/8
1"1/8
1"1/8
1"3/8
1"5/8
1"5/8
1"5/8
-2
0
2
4
1"1/8
1"1/8
1"1/8
1"3/8
1"3/8
2"1/8
2"1/8
-2
0
2
4
1"1/8
1"1/8
1"1/8
1"3/8
1"3/8
1"5/8
2"1/8
6
8
10
12
1"3/8
1"3/8
1"3/8
1"3/8
2"1/8
2"1/8
2"5/8
2"5/8
6
8
10
12
1"3/8
1"3/8
1"3/8
1"3/8
2"1/8
2"1/8
2"1/8
2"5/8
14
1"3/8
1"5/8
1"5/8
1"5/8
1"5/8
14
1"3/8
1"5/8
1"5/8
1"5/8
1"5/8
29