AIR CONDITIONER CAUTION OUTDOOR UNIT Read carefully all security information before use or install the air conditioner. Do not attempt to install the air conditioner or a part of the air conditioner by yourself. INSTALLATION MANUAL This unit must be installed by qualifi ed personnel with a capacity certifi cate for handling 9332809039 refrigerant fl...
Thicknesses of Annealed Copper Pipes Name Connection pipe assembly Maximum height Nominal Outer Maximum Connection cable Thickness (between indoor and out- diameter diameter length Wall pipe door) Decorative tape Vinyl tape 1/4 in 6.35 mm 0.8 mm 30 m (99 ft) 20 m (66 ft) Wall cap 5/8 in...
Connection cable wiring CAUTION Run the connection cable to the rear of the outdoor unit within the A range of the arrows shown in the fi gure. (The connector cover becomes diffi cult to install.) When the outdoor temperature is 0 ˚C or less, do not use the accessory drain pipe and drain cap.
FLARING Check if [L] is fl ared uniformly and Gauge manifold (1) Cut the connection pipe to the necessary is not cracked or scratched. Compound pressure gauge Pressure gauge length with a pipe cutter. -0.1 MPa (2) Hold the pipe downward so that cuttings will way valve 3-way valve (-76 cmHg...