Outdoor unit

Advertisement

When the outdoor temperature is 0 ˚C or less, do not use the accessory drain pipe
and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may
freeze in extreme cold weather. (Reverse cycle model only)
In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with
snow, it might become diffi cult to get warm and it is likely to cause of the breakdown.
Please construct a canopy and a pedestal or place the unit on a high stand (local
confi gured).

5. INSTALLATION

5.1. Outdoor unit installation
 Set the unit on a strong stand such as thing made of concrete blocks to minimize shock and vibration.
 Do not set the unit directly on the ground because it will cause trouble.
Install the unit where it will not be tilted by more than 5°.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
5.2. Connector cover remove
Connector cover
Tapping screw
Hooks
Tapping screw
5.3. Outdoor unit wiring
(1) Remove the outdoor unit connector cover.
(2) Bend the end of the cable as shown in the fi gure.
(3) Connect the end of the connection cable fully into the terminal block.
(4) Fasten the sheath with a cable clamp.
(5) Install the connector cover.
1
2
3
L
N
Earth
screw
Cable clamp
Indoor unit terminal block
1 2
3
Earth screw
En-3
CAUTION
WARNING
Connector cover removal
● Remove the tapping screws.
Installing the connector cover
(1) After inserting the four hooks, then push
upward.
(2) Tighten the tapping screws.
Cable clamp
Connection cable
Connection cable
Power supply cable
Outdoor unit terminal block
1
2
3
L
N
Earth screw
Connection cable
Power supply cable
Connection cable wiring
Run the connection cable to the rear of the outdoor unit within the A range of the arrows shown in the fi gure.
(The connector cover becomes diffi cult to install.)
How to fi xed connection cable and power supply cable at the cable clamp
After passing the connection cable and power supply cable through the insulation tube,
fasten it with the cable clamp.
Insulation tube
Use VW-1, 1.0 mm thick, PVC tube as the insulation tube.
5.4. HOW TO CONNECT THE WIRE TO THE TERMINALS
(1) Use crimp-type terminals with insulating sleeves as shown in the fi gure below to con-
nect to the terminal block.
(2) Securely crimp the crimp-type terminals to the wires using an appropriate tool so that
the wires do not come loose.
(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the
screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Tightening torque
M4 screw
M5 screw
Strip
10 mm
Screw with special washer
Wire
Crimp-type terminal
Terminal board
Terminal block
Screw with special washer
Crimp-type terminal
Match the terminal block numbers and connection cable colors with those of the indoor
unit.
Erroneous wiring may cause burning of the electric parts.
Connect the connection cables fi rmly to the terminal block. Imperfect installation may
cause a fi re.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric leakage may occur.)
Securely earth the power cable plug.
Do not use the earth screw for an external connector. Only use for interconnection
between two units.
5.5. Connecting the piping
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation set or pro-
cured at the site) to the wall pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the fl are surface and tightening the nut hand tight,
tighten the nut to the specifi ed tightening torque with a torque wrench. (Table 1)
Connection cable
Hole
8 cm
A 10 cm
Cable clamp
Insulation tube
1.2 to 1.8 N • m (12 to 18 kgf • cm)
2.0 to 3.0 N • m (20 to 30 kgf • cm)
Crimp-type terminal
Sleeve
CAUTION
Wire