Amana ASZ 14 SEER Technical Manual page 39

Split system asz 14 seer;
Table of Contents

Advertisement

HEATING SPECIFICATIONS
Model: ASZ140421A* / CA*F4860*6A*+TXV / MBR2000**-1
Conditions: 1400 CFM Indoor Air @ 70°F DB
Basic Unit without
Outdoor
Auxiliary Heat
Ambient
capacity
°F.
btuh
c.o.p.
65
51.54
4.44
60
48.79
4.28
55
45.92
4.11
50
42.93
3.92
45
39.73
3.70
40
36.90
3.50
35
34.03
3.30
30
34.27
3.26
25
31.63
3.08
20
29.12
2.90
15
26.48
2.70
10
23.76
2.48
5
21.07
2.25
0
18.37
2.01
-5
15.68
1.76
-10
12.84
1.48
Model: ASZ140601A* / CA*F4860*6A*+TXV / MBE2000**-1
Conditions: 1850 CFM Indoor Air @ 70°F DB
Basic Unit without
Outdoor
Auxiliary Heat
Ambient
capacity
°F.
btuh
c.o.p.
65
71.65
4.34
60
67.83
4.19
55
63.84
4.03
50
59.68
3.85
45
55.23
3.64
40
51.30
3.45
35
47.31
3.26
30
47.86
3.17
25
44.17
2.99
20
40.68
2.83
15
36.99
2.63
10
33.19
2.43
5
29.42
2.21
0
25.66
1.98
-5
21.90
1.74
-10
17.94
1.46
*To obtain BTU capacity of unit with KW of auxiliary heat, multiply by 1000 (Example: 39.01 x 1000 = 39,010 BTU)
Capacity of Unit*
With KW of Auxiliary heat
4.8
9.6
14.4
67.92
84.30
100.68
117.07
65.17
81.55
97.94
114.32
62.30
78.68
95.07
111.45
59.31
75.69
92.07
108.46
56.11
72.49
88.88
105.26
53.28
69.66
86.05
102.43
50.41
66.79
83.18
50.65
67.03
83.41
48.01
64.39
80.77
45.50
61.89
78.27
42.86
59.25
75.63
40.14
56.52
72.91
37.45
53.83
70.21
34.75
51.13
67.52
32.06
48.44
64.82
29.22
45.61
61.99
Capacity of Unit*
With KW of Auxiliary heat
4.8
9.6
14.4
88.03
104.41
120.80
137.18
84.21
100.59
116.98
133.36
80.22
96.60
112.99
129.37
76.06
92.44
108.83
125.21
71.62
88.00
104.38
120.76
67.68
84.06
100.45
116.83
63.69
80.07
96.46
112.84
64.24
80.63
97.01
113.39
60.56
76.94
93.32
109.70
57.06
73.44
89.83
106.21
53.37
69.76
86.14
102.52
49.57
65.95
82.34
45.81
62.19
78.57
42.04
58.42
74.81
38.28
54.66
71.04
34.32
50.70
67.09
Model: ASZ140481A* / CA*F4860*6A*+TXV / MBR2000**-1
Conditions: 1550 CFM Indoor Air @ 70°F DB
Basic Unit without
Outdoor
Auxiliary Heat
Ambient
capacity
°F.
btuh
19.2
65
57.82
60
54.74
55
51.52
50
48.16
45
44.57
40
41.40
35
38.18
99.56
30
36.62
99.79
25
33.80
97.15
20
31.12
94.65
15
28.30
92.01
10
25.39
89.29
5
22.51
86.59
0
19.63
83.90
-5
16.75
81.20
-10
13.72
78.37
Model: ASZ140361B* / AR*F374316B*+TXV -1
Conditions: 1250 CFM Indoor Air @ 70°F DB
Basic Unit without
Outdoor
Auxiliary Heat
Ambient
capacity
°F.
btuh
19.2
65
41.48
60
39.27
55
36.96
50
34.55
45
31.98
40
29.70
35
27.39
30
24.92
25
23.00
20
21.18
15
19.26
98.72
10
17.28
94.95
5
15.32
91.19
0
13.36
87.43
-5
11.40
83.47
-10
9.34
Capacity of Unit*
With KW of Auxiliary heat
c.o.p.
4.8
9.6
4.25
74.20
90.59
106.97
4.10
71.12
87.50
103.89
3.94
67.90
84.28
100.67
3.76
64.54
80.93
3.55
60.96
77.34
3.36
57.78
74.16
3.17
54.56
70.94
2.94
53.00
69.38
2.77
50.18
66.56
2.61
47.50
63.89
2.43
44.68
61.06
2.24
41.77
58.16
2.03
38.89
55.28
1.82
36.01
52.40
1.59
33.13
49.52
1.34
30.11
46.49
Capacity of Unit*
With KW of Auxiliary heat
c.o.p.
4.8
9.6
4.11
57.86
74.24
90.63
3.96
55.65
72.03
88.42
3.80
53.34
69.72
86.11
3.62
50.93
67.31
83.70
3.41
48.36
64.74
81.13
3.23
46.08
62.46
78.85
3.04
43.77
60.15
76.54
2.49
41.30
57.68
74.07
2.35
39.38
55.76
72.15
2.21
37.56
53.94
70.33
2.06
35.64
52.02
68.41
1.89
33.66
50.04
66.43
1.71
31.70
48.08
64.47
1.53
29.74
46.12
62.51
1.34
27.78
44.16
60.55
1.13
25.72
42.10
58.49
19.2
14.4
123.35
120.27
117.05
97.31
113.69
93.72
110.10
90.55
106.93
87.33
103.71
85.76
102.15
82.94
99.32
80.27
96.65
77.45
93.83
74.54
90.92
71.66
88.04
68.78
85.16
65.90
82.28
62.87
79.25
19.2
14.4
107.01
104.80
102.49
100.08
97.51
95.23
92.92
90.45
88.53
86.71
84.79
82.81
80.85
78.89
76.93
74.87
39

Hide quick links:

Advertisement

Table of Contents
loading