Gas Heat Troubleshooting Guide - York Sunline Magnum DJ180 Installation Manual

Sunline magnum gas/electric single package air conditioners
Hide thumbs Also See for Sunline Magnum DJ180:
Table of Contents

Advertisement

284809-YIM-B-0707

GAS HEAT TROUBLESHOOTING GUIDE

Troubleshooting of components may require
opening the electrical control box with the
power connected to the unit. Use extreme
care when working with live circuits! Check
the unit nameplate for the correct line voltage
and set the voltmeter to the correct range
before making any connections with line termi-
nals.
For troubleshooting of optional VFD, discon-
nect all power to the drive. Be aware that high
voltages are present in the drive even after
power has been disconnected. Capacitors
within the drive must be allowed to discharge
before beginning service.
When not necessary, shut off all electric power
to the unit prior to any of the following mainte-
nance procedures so as to prevent personal
injury.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause
improper and dangerous operation, which
could cause injury to person and/or damage
unit components. Verify proper operation after
servicing.
To find the Btu input, multiply the number of
NOTE:
cubic feet of gas consumed per hour by the
Btu content of the gas in your particular locality
(contact your gas company for this information
- it varies widely from city to city.).
The furnace may shut down on a high tem-
perature condition during the procedure. If
this occurs, the UCB energize the supply air
blower motor until the high temperature limit
has reset.
Caution should be used at all
times as the supply air blower may energize
regardless of the room thermostat fan switch
position.
Unitary Products Group
On calls for heating, the draft motor operates and the
furnace lights but the supply air blower motor does not
energize after a short delay (the room thermostat fan
switch is in "AUTO" position).
1. Place the thermostat fan switch in the "ON" posi-
tion. If the supply air blower motor energizes, go to
Step 9.
2. If the supply air blower motor does not energize
when the fan switch is set to "ON," check that line
voltage is being supplied to the contacts of the M3
contactor, and that the contactor is pulled in. For
units with VFD, check that line voltage is being
supplied to the M3-Auxiliary contacts. Check for
loose wiring between the contactor and the supply
air blower motor.
3. If M3 is pulled in and voltage is supplied at M3,
lightly touch the supply air blower motor housing. If
it is hot, the motor may be off on inherent protec-
tion. Cancel any thermostat calls and set the fan
switch to "AUTO", wait for the internal overload to
reset. Test again when cool.
4. If M3 is not pulled in, check for 24 volts at the M3
coil. If 24 volts is present at M3 but M3 is not pulled
in, replace the contactor.
5. Failing the above, if there is line voltage supplied at
M3, M3 is pulled in, and the supply air blower
motor still does not operate, replace the motor.
For units with VFD, if there is line voltage supplied
at M3, M3 is pulled in, and the blower motor does
not operate, check all power & control wiring con-
nections to and from the drive and for any fault/
warning messages displayed on the drive's digital
display (refer to the drive user manual for full
descriptions, if necessary). Clear any fault by
pressing 'RESET' on the drive's keypad and take
any corrective action as needed. If the motor still
does not operate, replace the motor.
6. If 24 volts is not present at M3, check that 24 volts
is present at the supply air blower motor terminal
on the UCB. If 24 volts is present at the UCB termi-
nal, check for loose wiring between the UCB and
M3.
a.
If 24 volts is not present at the UCB supply air
blower motor terminal, check for 24 volts from the
room thermostat. If 24 volts is not present from the
room thermostat, check for the following:
61