Lennox Commercial TouchScreen Thermostat Installation Instructions Manual page 9

Commercial touch screen thermostat
Hide thumbs Also See for Commercial TouchScreen Thermostat:
Table of Contents

Advertisement

Installer
Installer
Setup No.
Setup Name
Minimum
Compressor
0580
Off Time
Heat Tempera-
ture Range
0600
Stops
Cool Tempera-
ture Range
0610
Stops
0640
Clock Format
Extended Fan−
0650
on time Heat
Extended Fan−
0660
on time Cool
Keypad Lock-
0670
out
Temperature
0680
Control Heat
Temperature
0690
Control Cool
Recovery
0685
Heat Ramp
Rate
Recovery Cool
0695
Ramp Rate
Temperature
0700
Display Offset
Restore Fac-
0710
tory Defaults
Table 3. Installer Setup Menu
Default
All Settings
Setting
0− Off
2− 2 minutes
0
3− 3 minutes
4− 4 minutes
5− 5 minutes
90
40 to 90° F (4 to 32° C)
50
50 to 99°F (10 to 37°C)
12
12−12 Hour 24− 24 Hour
0−Off
0
90− 90 seconds
0−Off
0
40− 40 seconds
0−Unlocked
1−Partial Lockout 1
0
2−Partial Lockout 2
3−Fully Locked
1−Less Aggressive
2
2−Standard
3−More Aggressive
1−Less Aggressive
2−Standard
2
3−More Aggressive
5
0−20°F/hour
3
0−20°F/hour
−3 (−1.5) −3°F(−1.5°C)
−2 (−1.0)− −2°F (−
1.0°C)
−1 (−0.5)− −1°F (−0.5°C)
0
0 (0.0)−0°F (0.0°C)
1 (0.5)−1°F (0.5°C)
2 (1.0)− 2°F (1.0°C)
3 (1.5)−3°F (1.5°C)
0 −No
0
1−Yes
Page 9
Notes
Only shown if system has cool stages. Set to
0. Not needed for 3 phase systems.
Only shown if system has heat stages.
Only shown if system has cool stages.
Not displayed with fan set to fossil or with cool−
only systems.
Only shown if system has cool stages.
Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and
Up/Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non−functional.
Only shown if system has heat stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recov-
ery or setpoint change).
More Aggressive stops signal prior to reaching
the setpoint. (For use with oversized equip-
ment.)
Only shown if system has cool stages.
Only integral gains affected. Affects control
operation in all control regimes (not just recov-
ery or setpoint change).
More Aggressive stops signal prior to reaching
the setpoint. (For use with oversized equip-
ment.)
Only shown if system has heat stages.
0 disables ramped recovery (step setpoint
change at period start time).
Only shown if system has cool stages.
0 disables ramped recovery (step setpoint
change at period start time).
This offset applies to both the control tempera-
ture and to the display temperature for indoor
sensor (and remote indoor sensor).
Resets all ISU parameters to default values
and resets the schedule to default Energy Star.
Retains only calendar settings and time.