HIGH ALTITUDE DERATE CHART - MAIN BURNER ORIFICE SIZE
60,000 BTU FURNACE
ELEVATION
PART NO
ORIF DIA
SEA LEVEL
75AG-144
0.144
2000
75AG-1405
0.1405
3000
75AG-1405
0.1405
4000
75AG-136
0.136
5000
75AG-136
0.136
6000
75AG-136
0.136
7000
75AG-1285
0.1285
8000
75AG-1285
0.1285
9000
75AG-1285
0.1285
10000
75AG-120
0.120
ELEVATION
60,000 BTU FURNACE
PART NO
ORIF DIA
SEA LEVEL
75AG-086
0.086
2000
75AG-082
0.082
3000
75AG-082
0.082
4000
75AG-082
0.082
5000
75AG-081
0.081
6000
75AG-0785
0.0785
7000
75AG-0785
0.0785
8000
75AG-076
0.076
Table shows 4% Input Reduction per 1,000 feet elevation
Reference: NFPA No. 54, ANSI Z 223.1 National Fuel Gas Code
For canadian High Alitude (2,000-4,500 feet), reduce gas pressure to burner manifold (manifold Ps.) to 3.0" W.C. for Natural Gas and 9.0 W.C. for LP (Propane) Gas
HIGH ALTITUDE ORIFICE CONVERSION KITS
KIT PART NUMBER
ALTITUDE
G18HA0601
0 - 5000 FT
G18HA0602
6,000 - 10,000 FT
G18HA0701
0 - 5000 FT
G18HA0702
6,000 - 10,000 FT
G18HA0771
0 - 5000 FT
G18HA0772
6,000 - 10,000 FT
G18HA0901
0 - 5000 FT
G18HA0902
6,000 - 10,000 FT
Winchester by Mortex Products Inc. / Fort Worth, TX 76106