Fitting The Code Plug; Fitting The Cylinder Temperature Sensor; Diverter Valve And Sensor Connections - Worcester Gas boiler Installation Instructions Manual

Wall hung rsf gas fired condensing boiler greenstar i system optional integral diverter valve for central heating systems and indirect fed domestic hot water
Table of Contents

Advertisement

4.3

FITTING THE CODE PLUG

Boiler size
12kW i System kit
15kW i System kit
18kW i System kit
24kW i System kit
1. Refer to figure 14. Remove the code plug from the
controller, cut the tie securing the plug to the boiler
chassis and discard the plug and tie.
2. Fit the code plug from the kit making sure that code
plug is secured to the boiler chassis with the new tie.
B Confirm that the number on the code plug
corresponds to the boiler type in the table above.
2.
ST18
Fig. 14 Fitting new code plug
4.4
FITTING THE CYLINDER
TEMPERATURE SENSOR
Refer to the cylinder installation instructions for the
position of the sensor, there may already be a "sensor
pocket" available. If no "pocket" is available, for foam
insulated cylinders only with no metal jacket, follow the
steps below.
1. Mark a rectangular hole of approximately 50 by
100mm approximately one third of the cylinder length
from the bottom of the cylinder.
CAUTION: Cut carefully!
B Do not to pierce the wall of cylinder.
B Do not cut any metal insulation jacket.
1. Using a sharp knife, cut through the insulation,
remove and retain the piece of insulation.
2. Apply heat conductive paste to the sensor and place
the sensor on the cylinder body in the middle of the
cut-out.
3. Hold the sensor in position with a piece of aluminium
tape.
4. Replace the insulation material.
5. Secure the insulation in place with suitable cloth
tape.
6 720 645 222a (2012/05)
Gas
Code plug no.
NG
1118
LPG
1119
NG
1122
LPG
1123
NG
1126
LPG
1127
NG
1114
LPG
1115
1.
6720645222-10.1Wo
FITTING THE DIVERTER VALVE AND CODE PLUG
NOTICE: Figure 15 applies only to foam
covered open vent cylinders.
6.
Fig. 15 Sensor connection to cylinder
4.5
DIVERTER VALVE AND SENSOR
CONNECTIONS
NOTICE: Do not route low voltage cables
alongside mains voltage cables.
This can cause interference on the low
voltage cables.
1. Connect the Diverter valve motor harness to the edge
connector ST17.
2. Connect the cylinder temperature sensor (1) to the
edge connector ST15.
If the ST15 connector and sensor is being
used do not connect ST8 as well.
The link is not required.
ST15
ST17
Fig. 16 Diverter motor and sensor connections
B Replace the control panel cover.
B Move the control panel to the up position and secure.
1.
2.
3.
4.
5.
6720645222-24.1Wo
2.
1
1.
6720645222-11.1Wo
11