Do you want to view the programmable timer settings?
Press the
button to sequentially review the 8 auto timers.
Do you want to reload the default timer settings?
1.
Set the controller to protection mode
+
2.
Press
and
simultaneously for 3 seconds. Release them and, within 2
seconds, press 2 times
.
Day/s
Time when controller is in normal operation
Mo (1) – Fr (5)
06:30 – 08:30 (A1)
Default
Sa (6)
settings
Su (7)
- in the remaining time controller is in energy saving
- timer A5...A8 are free, no default setting
Changing the control parameters
To optimize the control performance, a number of control parameters can be adjusted. This can
also be made during operation without opening the controller.
If you want to change the control parameters, proceed as follows:
(For factory settings, see table on the right-hand side)
+
1. Set the controller to protection mode
/
2. Press
and
simultaneously for a minimum of 3 and a
maximum of 5 seconds. Release them and, within 2 seconds, press
the
again for 3 seconds. The display will show "P01".
3. Select the required parameter by repeatedly pressing the
+
-
+
+
-
P01
P02
3075Z03
+
4. By pressing
and
simultaneously, or by pressing
value of the selected parameter appears, which can be changed by repeatedly
pressing
or
.
+
5. 5 seconds after the last press of a button, or by pressing
simultaneously, the value will be stored.
6. If you wish to display and change additional parameters,
repeat steps 3 through 5.
7. 10 seconds after the last display or setting, all changes are
stored and the controller will return to standby.
8.
Switch to comfort operation
CE1B3075en / 31.10.2008
.
17:30 – 22:30 (A2)
08:00 – 23:00 (A3)
08:00 – 22:30 (A4)
or
button:
+
-
P18
, the current
and
with the
button.
Changing the batteries
1.
Get 2 new batteries of type AA alkaline, 1.5 volts.
2.
Within 1 minute: Remove the battery holder, then the batteries, insert new batteries and replace the battery holder.
3.
Make certain the old batteries are disposed of properly, in compliance with environmental requirements.
Recalibrating the sensor
If the room temperature displayed by the controller does not agree with the temperature effectively measured, the temperature sensor can be
recalibrated. For that purpose parameter P07 must be changed.
Proceed as described under "Changing the control parameters" and follow steps 1 through 3 to select parameter P07.
With step 4, the room temperature displayed can now be matched to the temperature effectively measured. Each push of the
button changes the temperature by + or – 0.5 °C up to a maximum of + / - 3 °C. With step 7, the recalibration is automatically stored 10
seconds after the last readjustment.
Commissioning (by qualified HVAC staff)
Para-
Controller's parameter factory settings:
meter
P01
Setpoint of heating in energy saving mode
P02
Setpoint of cooling in energy saving mode
P03* Setpoint of heating in protection mode
P04* Setpoint of cooling in protection mode
P05
Min. setpoint limitation in Comfort mode
P06
Max. setpoint limitation in Comfort mode
P07
Sensor calibration
P08
Switching differential heating SDH
P09
Switching differential cooling SDC
P10
Setpoint differential between heating & auxiliary heating W
P11
Minimum compressor on-time (Q14)
P12
Minimum compressor off-time (Q14)
P13
Auxiliary heater minimum hold-time
P14
Selection of °C or °F
P15
Display of temperature or setpoint
P16
Auxiliary heater in heating mode
P17
Time format option
P18
Operating action changeover heating/cooling Q21 - Q22
Legend to table
Adjustable: Please record all changes you make
P03* / P04*:
P04 is at least min. 5 K higher than P03
Energy saving tips without sacrificing comfort
Never allow room temperatures to exceed 21˚C.
Air out rooms for short periods of time only, but properly, with the windows wide open.
Subject to alteration
(all temperature settings can be made in increments of 0.5 K and the time in increments of 1 min.)
Setting range , step
(W heat
)
16
OFF, 5 °C...W cool
Eco
(W cool
)
28
OFF, W heat
Eco
8 °C
OFF, 5 °C...W cool
(W heat
)
PROT
OFF
OFF, W heat
(W cool
)
PROT
5 °C
5...40 °C, 0.5 K
(W min
)
Comf.
35 °C
5...40 °C, 0.5 K
(W max
)
Comf.
0 K
-3...+3 K, 0.5 K
2 K
0.5...+4K, 0.5 K
1 K
0.5...+4K, 0.5 K
2 K
0.5...+5K, 0.5 K
D
1 min.
1...10 minutes, 1 min.
3 min.
1...10 minutes, 1 min.
1 min.
1...10 minutes, 1 min.
°C
C or °F
OFF: Setpoint
ON
ON: Room temperature
0: Disable
1: Enable
1: Enable
0: 12 hour format
1: 24 h
1: 24 hour format
0: Open (heating), close
(cooling)
0:
1: Close (heating), open
(cooling)
Not adjustable / display only
or
RDX33
RDX43
, 0.5 K
Eco
...40 °C, 0.5 K
Eco
, 0.5 K
PROT
...40 °C, 0.5 K
PROT
X
X
X
X
Not available