5

4-WAY AIR FLOW SYSTEM

5-1. PLACEMENT OF THE AIR OUTLETS
• For this grille, the blowout direction comes in 11 patterns.
Also, by setting the remote controller to the appropriate settings, you can adjust the airflow and speed. Select the settings
from Table1 according to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
<Table 1>
4-direction
Pattern 1
Initial setting
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to set up the switches
(SWA, SWB) on the circuit board to the appropriate setting.
• Correspondence of ceiling heights to numbers of air outlets
PLFY-P32·P40·P50·P63·P80VBM-E
SWA
Silent
SWB
4
4 direction
2.5m
3
3 direction
2.7m
2
2 direction
3.0m
PLFY-P100·P125VBM-E.UK
SWA
Silent
SWB
4
4 direction
2.7m
3
3 direction
3.0m
2
2 direction
3.3m
3-direction
Pattern 4
1 air outlet
fully closed
.UK
(1)
1
2
Standard
High ceiling
2.7m
3.0m
3.3m
1
2
Standard
High ceiling
3.2m
3.6m
4.0m
2-direction
Pattern 6
2 air outlet
fully closed
3
3.5m
3.5m
3.5m
3
4.5m
4.5m
4.5m
13
Note1.
For 3 and 2-direction
settings, please use
the air outlet shutter
plate (option).