Circulating Air And Filters; Ductwork-Airflow - Whirlpool WGFD28 Installation Instructions Manual

80% 2-stage variable speed gas furnace gold models
Table of Contents

Advertisement

Sizing Between 2
nd
Stage and Appliance Regulator*
Maximum Propane Capacities Listed are Based on ¹⁄₂" W.C. pressure drop at 10.0" W.C. setting. Capacities in 1,000 Btu/h.
Propane Gas Piping Chart II
Pipe or Tubing Length—ft (m) ³⁄₈"
10 (3)
20 (6.1)
30 (9.2)
40 (12.2)
50 (15.2)
60 (18.3)
80 (24.4)
100 (30.5)
125 (38.1)
150 (45.7)
200 (61)
250 (76.2)
Data in accordance with NFPA pamphlet Number 54.
WARNING
Never allow the products of combustion, including carbon
monoxide, to enter the return ductwork or circulation air
supply.
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rating of the furnace.
Design the ductwork in accordance with the recommended
methods of "Air Conditioning Contractors of America"
Manual D.
Install the duct system in accordance with Standards of the
National Board of Fire Underwriters for the Installation of Air
Conditioning, Warm Air Heating and Ventilating Systems.
Pamphlets No. 90A and 90B.
A closed return duct system must be used with the return
duct connected to the furnace.
NOTE: Ductwork must never be attached to the back of the
furnace.
For installations requiring more than 1,800 CFM, use either
2 side returns or bottom return.
Flexible joints may be used for supply and return connections
to reduce noise transmission.
20
Tubing Size, O.D. Type L
¹⁄₂"
⁵⁄₈"
³⁄₄"
39
92
199
329
26
62
131
216
21
50
107
181
19
41
90
145
18
37
79
131
16
35
72
121
13
29
62
104
11
26
55
90
10
24
48
81
9
21
43
72
8
19
39
66
8
17
36
60

CIRCULATING AIR AND FILTERS

Ductwork—Airflow
Nominal Pipe Size Schedule 40
⁷⁄₈"
¹⁄₂"
1¹⁄₈"
501
935
275
346
630
189
277
500
152
233
427
129
198
376
114
187
340
103
155
289
89
138
255
78
122
224
69
109
202
63
100
187
54
93
172
48
To prevent the blower from interfering with combustion air or
draft when a central return is used, a connecting duct must
be installed between the unit and the utility room wall.
Never use a room, closet or alcove as a return air chamber.
When the furnace is installed with a cooling unit, the furnace
should be installed in parallel with or on the upstream side of the
cooling unit to avoid condensation in the heating element. With a
parallel flow arrangement, the dampers or other means used to
control the flow of air must be adequate to prevent chilled air
from entering the furnace and, if manually operated, must be
equipped with means to prevent operation of either unit unless
the damper is in the full heat or cool position.
When the furnace is installed without a cooling unit, it is
recommended that a removable access panel be provided in the
outlet air duct. This opening shall be accessible when the furnace
is installed and shall be of such a size that the heat exchanger
can be viewed for visual light inspection or such that a sampling
probe can be inserted into the airstream. The access panel must
be made to prevent air leaks when the furnace is in operation.
When the furnace is heating, the temperature of the return air
entering the furnace must be between 55°F and 100°F (13ºC and
38ºC).
When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by a duct sealed
to the furnace casing and terminating outside the space
containing the furnace.
³⁄₄"
1"
1¹⁄₄"
1¹⁄₂"
567
1,071
2,205
3,307
393
732
1,496
2,299
315
590
1,212
1,858
267
504
1,039
1,559
237
448
913
1,417
217
409
834
1,275
185
346
724
1,066
162
307
630
976
146
275
567
866
132
252
511
787
112
209
439
665
100
185
390
590

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wgfm28

Table of Contents