Heat Controller HBH Series Installation, Operation & Maintenance Manual page 41

Commercial horizontal packaged water source heat pump 6-10 tons hbh series;
Hide thumbs Also See for HBH Series:
Table of Contents

Advertisement

Heat Controller, Inc.
Unit Operating Conditions
Operating Pressure/Temperature tables include the
following notes:
• Airflow is at nominal (rated) conditions;
• Entering air is based upon 70°F [21°C] DB in heating
and 80/67°F [27/19°C] in cooling;
Table 11: HB Series Typical Unit Operating Pressures and Temperatures (60Hz - I.P. Units)
Entering
Water
Suction
Water
Flow
Pressure
Temp °F
GPM/ton
PSIG
1.5
20
2.25
3
1.5
122 - 125
*
2.25
116 - 119
30
3
112 - 115
1.5
128 - 134
50
2.25
122 - 131
3
119 - 129
1.5
132 - 139
70
2.25
131 - 137
3
131 - 136
1.5
137 - 144
90
2.25
135 - 142
3
135 - 141
1.5
139 - 147
100
2.25
138 - 146
3
138 - 146
1.5
144 - 153
120
2.25
143 - 153
3
143 - 152
*Based on 15% Methanol antifreeze solution
NOTE: The tables include the following notes:
Airflow is at nominal (rated) conditions;
Entering air is based upon 70°F [21°C] DB in heating and
80/67°F [27/19°C] in cooling;
Subcooling is based upon head pressure at compressor
service port;
Cooling air and water values can vary greatly with
changes in humidity level.
Table 12: Water Temperature Change Through Heat
Exchanger
Water Flow, gpm [l/m]
For Closed Loop: Ground Source or
Closed Loop Systems at 3 gpm per
ton [3.2 l/m per kW]
For Open Loop: Ground Water
Systems at 1.5 gpm per ton
[1.6 l/m per kW]
Cooling
Discharge
Pressure
Superheat
Subcooling
PSIG
197 - 204
13 - 16
15 - 20
177 - 184
17 - 19
15 - 18
168 - 173
19 - 21
14 - 18
240 - 252
11 - 14
13 - 16
219 - 233
12 - 17
12 - 16
209 - 224
13 - 18
11 - 15
311 - 329
9 - 12
12 - 15
287 - 306
10 - 13
10 - 12
275 - 294
10 - 13
9 - 11
400 - 420
8 - 10
13 - 16
373 - 395
9 - 11
10 - 12
359 - 383
9 - 12
9 - 11
448 - 471
8 - 9
13 - 16
420 - 445
8 - 10
11 - 13
405 - 432
8 - 10
10 - 11
549 - 583
7 - 8
15 - 17
525 - 557
7 - 8
12 - 14
511 - 543
8 - 9
11 - 13
Rise, Cooling
Drop, Heating
°F, [°C]
°F, [°C]
9 - 12
[5 - 6.7]
[2.2 - 4.4]
20 - 26
10 - 17
[11.1 - 14.4]
[5.6 - 9.4]
HBH SERIES
• Subcooling is based upon head pressure at compressor
service port;
• Cooling air and water values can vary greatly with
changes in humidity level.
Water
Air Temp
Suction
Temp Rise
Drop °F
Pressure
°F
DB
PSIG
60 - 63
20 - 24
22 - 23
67 - 71
13 - 16
21 - 22
71 - 75
10 - 12
21 - 22
74 - 76
20 - 22
21 - 22
97 - 102
13 - 15
21 - 22
104 - 108
10 - 11
21 - 22
107 - 122
19 - 21
20 - 21
130 - 135
13 - 14
20 - 21
139 - 144
9 -11
20 - 21
145 - 149
19 - 20
19 - 20
164 - 169
12 - 14
19 - 20
175 - 178
9 - 10
19 - 20
179 - 187
18 - 20
18 - 19
12 - 13
18 - 19
9 - 10
18 - 19
17 - 19
17 - 18
11 - 13
17 - 18
9 - 10
17 - 18
4 - 8
40
Heating
Discharge
Pressure
Superheat
Subcooling
PSIG
289 - 306
9 - 12
8 - 17
297 - 315
10 - 12
9 - 18
301 - 321
10 - 12
10 - 19
303 - 323
11 - 13
10 - 19
333 - 355
9 - 11
13 - 21
339 - 361
9 - 11
13 - 21
342 - 369
9 - 11
13 - 20
367 - 392
9 - 11
13 - 21
375 - 402
10 - 11
13 - 20
380 - 407
10 - 11
13 - 19
401 - 430
10 - 13
13 - 17
411 - 442
12 - 16
14 - 17
415 - 455
13 - 18
14 - 16
IOM Manual
Water
Air Temp
Temp Drop
Rise °F DB
°F
3 - 4
20 - 22
8 - 9
22 - 23
6 - 7
23 - 24
4 - 5
23 - 25
11 - 12
29 - 30
8 - 9
30 - 31
6 - 7
31 - 32
14 - 16
35 - 37
10 - 12
37 - 38
8 - 9
38 - 39
18 - 20
41 - 43
12 - 14
43 - 45
9 - 11
44 - 46