Climatic™50 Input/ Output Mapping - Lennox CLIMATIC 50 User Manual

Table of Contents

Advertisement

TM
CLIMATIC
50 Mapping
Ecologic 'WA'
Digital Input
-J5.ID1: C1 – Comp. –Fault
-J5.ID2: C1 – HP
-J5.ID3: C1/C2 – Ventil. –Fault
-J5.ID4: C2 – Comp. –Fault
-J5.ID5: C2 – HP
-J5.ID6: Water – Flow
-J5.ID7: ON/OFF / Remote Control
-J5.ID8: Reset / Remote Control
-J7.ID9: Safety Elec Pump 1&2
-J7.ID10: Step 1 (RA)
-J7.ID11: Step 2 (RA)
-J7.ID12: Step 3 (RA)
-J8.ID13: Step 4 (RA)
-J8.ID14: Step 5 (RA)
-J4.ID1: Energy recovery Unit or Custom 1
-J4.ID2: Custom 2 – BE50.1
-J4.ID3: Custom 3 – BE50.2
-J4.ID4: Custom 4 – BE50.3 or stater
CLIMATIC 50 user manual – Chillers ranges
Digital Output
-J12.NO1: C1 – Compressor 1
-J12.NO2: C1 – Compressor 2
-J12.NO2: C1 – MCC/MCW Valve Cp1
-J12.NO3: C1 – WA Compressor 3
-J12.NO3: C1 – MCC/ If two speed, fan 3
-J13.NO4: C2 – Compressor 1
-J13.NO5: C2 – WA Compressor 2
-J13.NO5: C2 - MCC/MCW Valve Cp1
-J13.NO6: C2 – Compressor 3
-J13.NO6: C2 - MCC/ If two speed, fan 3
-J14.NO7: Water – Pump 1
-J15.NO8: C1 – Ventilation 1
-J15.NO8: C1 – Ventilation 1 – High.Speed
-J15.NC8: C1 – Ventilation 1 – Low.Speed
-J16.NO9: C1 – Bypass Valve
-J16.NO9: C1 – 4 Way Valve
-J16.NO10: C2 – Bypass Valve
-J16.NO10: C2 – 4 Way Valve
-J16.NO11: Water – Pump 2
-J17.NO12: C2 – Ventilation 1
-J17.NO12: C2 – Ventilation 1–High.Speed
-J17.NC12: C2 – Ventilation 1–Low.Speed
-J18.NO13: General Alarm
-J5.NO1: MCC C1 - Fan 2
-J5.NO1: MCC C1 – Fan 1 if two speeds
-J5.NO1: free cooling
-J5.NO1: Custom BE50.1
-J6.NO2: MCC C1 - Fan 3
-J6.NO2: MCC C1 – Fan 2 if two speeds
-J6.NO2: Custom BE50.2
-J7.NO3: MCC C2 - Fan 2
-J7.NO3: MCC C2 – Fan 1 if two speeds
-J7.NO3: Custom BE50.3
-J8.NO4: Starter
-J8.NO4: MCC C2 - Fan 3
-J8.NO4: MCC C2 – Fan 2 if two speeds
-J8.NO4: Custom BE50.4
BM50 – Base Board
Analogic Input
-J2.B1: C1 – HP (4~20ma -1~29b)
-J2.B2: C1 – BP (4~20ma -1~6b) *
-J2.B3: C2 – HP (4~20ma -1~29b)
-J2.B4: C2 – BP (4~20ma -1~6b) *
-J3.B5: Water – Outlet (NTC)
-J3.B6: Water – Inlet (NTC)
-J6.B7: MCW Water T cond Outlet
-J6.B8: Outdoor Air (NTC)
* If No Electronic Exp Valve
BE50 – Extension Board
-J9.B1: WAH C1 - Discharge T° Comp1 (NTC150°C)
-J9.B1: WA - Energy recovery Inlet (NTC)
-J9.B1: Custom BE50.1
-J9.B2: WAH C1 - Discharge T° Comp2 (NTC150°C)
-J9.B2: WA - Energy recovery Onlet (NTC)
-J9.B2: Custom BE50.2
-J10.B3: WAH C2 - Discharge T° Comp1 (NTC150°C)
-J10.B3: Custom BE50.3
-J10.B4: WAH C2 - Discharge T° Comp2 (NTC150°C)
-J10.B4: Custom BE50.4
CL50-CHILLERS/IOM/1105-E
Analogic Output
-J4.Y1: C1 – Ventilation 2, 3, 4
-J4.Y1: C1 – Ventilation 1, 2, 3 if two speed
-J4.Y2: C2 – Ventilation 2, 3, 4
-J4.Y2: C2 – Ventilation 1, 2, 3 if two speed
-J4.Y3: C1 – Ventilation 1 – PWM
-J4.Y4: C2- Ventilation 1 – PWM
-J2.Y1: Free cooling