Pre-Installation Checklist - Joslyn JSP series Installation, Operation And Maintenance Manual

Surge protective devices
Table of Contents

Advertisement

JoslyN
JsP
iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl
®
TM

Pre-Installation Checklist

tnbpowersolutions.com/joslynsurge
confirm that the voltage(s) and service configuration shown on the JsP
product label are consistent with the voltage and service configuration of
the facility . A model number is on the right side of the JsP unit . each model
number corresponds to the configurations printed in Table 1:
example of a sPD model number: JsP160-3y208-F
sample Model Number scheme
J S P
1 6 0 — 3 y
MODeL
1
JsPxxx-1P120
JsPxxx-1P240
1
1
JsPxxx-1s240
JsPxxx-3y208
1
JsPxxx-3y380
1
1
JsPxxx-3y415
JsPxxx-3y480
1
JsPxxx-3H240
1
JsPxxx-3y600
JsPxxx-3D240
1
JsPxxx-3D380
JsPxxx-3D480
JsPxxx-3D600
Options Suffixes
F
B
s
M
1
These are the only voltages available on the 60, 80, and 100kA systems.
NOTES:
• xxx denotes surge rating per phase (60, 80, 100, 120, 160, 200, 240, 300, 400)
• The power system operation frequency is between 47–63Hz.
confirm that the environmental conditions are consistent with the
following ranges:
• Ambient Temperatures: Between -40° and +158°F (-40º to 70º c) .
• relative Humidity: Between 5% and 95% non-condensing .
• Altitude: less than 13,000 feet (4000 m) .
2 0 8 — F
Table 1: Configuration Table
NOMINAL
L-N
vOLTAGe
vOLTAGe
vOLTAGe
RANGe
RANGe
120
90-132
90-132
240
180-264
180-264
120/240
90-132
180-280
120/208
312-382
540-660
220/380
198-253
342-440
240/415
216-264
373-457
277/480
249-305
432-528
108-132 (A, c)
120/240
216-264
187-229 (B)
347/600
313-394
540-660
240
N/A
216-264
380
N/A
342-418
480
N/A
432-528
600
N/A
540-660
Transient filter that meets ul 1283
(Not recommended when using telecommunication rectifiers)
surge counter
NeMA 4X stainless steel enclosure
Advanced Monitoring
L-L
CONFIGURATION
1-Phase, 2-Wire + Ground
1-Phase, 2-Wire + Ground
split-Phase, 3-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, High-leg
4-Wire + Ground
3-Phase Wye, 4-Wire + Ground
3-Phase Delta, 3-Wire + Ground
3-Phase Delta, 3-Wire + Ground
3-Phase Delta, 3-Wire + Ground
3-Phase Delta, 3-Wire + Ground
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents