Pre-Installation Checklist

tnbpowersolutions.com/joslynsurge
Confirm that the voltage(s) and service configuration shown on the JSP Series
product label are consistent with the voltage and service configuration of the
facility . A model number is on the right side of the JSP Series unit . Each model
number corresponds to the configurations printed in Table 1:
Example of a SPD model number: JSP(R)160-3Y208-F
Sample Model Number Scheme
J S P ( R ) 1 6 0 — 3 Y
MODEL
JSP(R)xxx-1P120
1
1
JSP(R)xxx-1P240
JSP(R)xxx-1S240
1
1
JSP(R)xxx-3Y208
JSP(R)xxx-3Y380
1
JSP(R)xxx-3Y415
1
1
JSP(R)xxx-3Y480
JSP(R)xxx-3H240
1
JSP(R)xxx-3Y600
1
JSP(R)xxx-3D240
JSP(R)xxx-3D380
JSP(R)xxx-3D480
JSP(R)xxx-3D600
JSP Series Options
F
Transient filter that meets UL 1283 (Not recommended when using telecommunication rectifiers)
B
Surge Counter (not available on JSP 60–100kA units or the JSPR series)
S
NEMA 4X stainless steel enclosure
M
Advanced monitoring (available in 60–100kA units only)
1
These are the only voltages available on the 60, 80, and 100kA systems.
NOTES:
• xxx denotes surge rating per phase (60, 80, 100, 120, 160, 200, 240, 300, 400)
• JSPR units are only available in 120 and 160kA.
• The power system operation frequency is between 47–63Hz.
Confirm that the environmental conditions are consistent with the
following ranges:
• Ambient Temperatures: Between -40° and +158°F (-40º to 70º C) .
• Relative Humidity: Between 5% and 95% non-condensing .
• Altitude: Less than 13,000 feet (4000 m) .
2 0 8 — F
Table 1: Configuration Table
NOMINAL
L-N
VOLTAGE
VOLTAGE
VOLTAGE
RANGE
RANGE
120
108-132
N/A
240
216-264
N/A
120/240
108-132
216-204
120/208
108-132
187-229
220/380
198-242
342-418
240/415
216-264
374-457
277/480
249-305
432-528
108-132 (A, C)
120/240
216-264
187-229 (B)
347/600
312-382
540-660
240
N/A
216-264
380
N/A
342-418
480
N/A
432-528
600
N/A
540-660
L-L
CONFIGURATION
1-Phase, 2-Wire + Ground
1-Phase, 2-Wire + Ground
Split-Phase, 3-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, 4-Wire + Ground
3-Phase, High-Leg
4-Wire + Ground
3-Phase Wye, 4-Wire + Ground
3-Phase Delta, 3-Wire + Ground
3-Phase Delta, 3-Wire + Ground
3-Phase Delta, 3-Wire + Ground
3-Phase Delta, 3-Wire + Ground
4