Joslyn Surgitron I 1260 Installation, Operation And Maintenance Manual

Surge protective devices

Advertisement

Surgitron I
TM
S u r g e
P r O T e C T I O N
Installation, Operation
and Maintenance Manual
PN 750-0111-001 B00
Surge Protective Devices
Joslyn

Advertisement

Table of Contents
loading

Summary of Contents for Joslyn Surgitron I 1260

  • Page 1 Surgitron I Joslyn S u r g e P r O T e C T I O N Installation, Operation and Maintenance Manual PN 750-0111-001 B00 Surge Protective Devices...
  • Page 2: Table Of Contents

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Guide to Installation and Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Table of Contents The Importance of Correct Installation .
  • Page 3: Guide To Installation And Assistance

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Thank you for choosing the Joslyn Surgitron I Series Surge Protective Device ® Guide to Installation and Assistance (SPD) . We look forward to fulfilling your facilitywide surge protection needs . Should you have questions about installing the Surgitron I series please call Joslyn Technical Support at 800.238.5000 or 804.236.3300...
  • Page 4: Before Installation

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Confirm that the voltage(s) and service configuration shown on the product label are Before Installation: consistent with the voltage and service configuration of the facility . A model number System Configuration verification is on the right side of the unit . Each model number corresponds to the configurations printed in the table below: NOMINAL MODeL...
  • Page 5: Wiring Connection Diagrams

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Wiring Connection Diagrams Figure 1 Single-Phase, 2-Wire Models: 1260, 1261 Figure 2 Split-Phase, 3-Wire Model: 1265 Figure 3 3-Phase, 4-Wire Wye Models: 1455, 1456, 1457 Figure 4 3-Phase, 3-Wire Delta Models: 1450, 1451...
  • Page 6: 3-Phase, 4-Wire High-Leg Delta

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Figure 5 ORANGE 3-Phase, 4-Wire high-Leg Delta Model: 1452 Figure 6 3-Phase, 3-Wire Delta Corner Grounded Model: 1266 C A u T I O N ! Conductor Routing The Surgitron I’s performance will be limited severely if the conductors are (a) too long, (b) are of too small a wire gauge, (c) have too many bends or (d) have sharp bends.
  • Page 7: Upstream Overcurrent Protection Device

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl The Surgitron I has been listed to UL1449 as a Type 1 SPD . Type 1 SPDs upstream Overcurrent can be used in Type 1 or Type 2 SPD applications, which means that the Protection Device Surgitron I does not need to be connected behind an upstream Overcurrent protection device and can be connected on either the line or load side of the...
  • Page 8: Conductor Sizing

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Series Connecting: If the service conductors are AWG 2/0 or smaller than 70 Conductor Sizing , the protector can be series connected and brought directly through the protector enclosure (the terminals are double lugged) . This type of connection is the better as there is no Ldi/dt voltage drop (additive to the protector’s suppression voltage), as is associated with the shunt connection method of installation .
  • Page 9: Conduit Openings And Enclosure/Mounting Dimensions

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl Figure 7: Conduit Openings and enclosure/Mounting Dimensions 11.50" 10.75" 1260, 1261 4.20" 6.00" .31" Mounting Hole Ø 8.90" 4 Places 1265 13.50" 12.75" 5.20" 8.00" .31" Mounting Hole Ø 10.90" 4 Places Possible Locations for Conduit Holes Metal NEMA 4 (IP66) Enclosure 15.50"...
  • Page 10: Connecting Form "C" Dry Contacts

    Surgitron i inStAllAtion, operAtion AnD MAintenAnce MAnuAl All units with -80, or -85 in the suffix come standard with two sets of Form Connecting Form “C” “C” dry relay contacts for the surge protective device status . These contacts Dry Contacts are for connection to a user-provided remote alarm and monitoring circuit .
  • Page 11: Troubleshooting

    A Return Material Authorization (RMA) number must be obtained from T&B’s Customer Service department before replacement products can be shipped . INFORMATION eXAMPLe Model Number 1265-85 Serial Number 15478-0105-001 Date of Purchase January 2, 2005 (1st week) Description of Failure LED Out Desired Action from Joslyn Replace...
  • Page 12: Warranty Statement

    Thomas & Betts Power Solutions, LLC, A Member of the ABB Group (“Seller”) Warranty Statement warrants that your Joslyn surge protective device (the “Product”), shall meet applicable industry standards and specifications and be free from defects in materials and/or workmanship . Should any failure of the Product to conform to this warranty appear within the standard warranty period, Seller shall either repair or replace the defective Product, or part thereof, upon return to Seller’s...