Verification And Power Up - Joslyn JSP series Installation, Operation And Maintenance Manual

Surge protective devices
Table of Contents

Advertisement

JoslyN
JsP
iNsTAllATioN, oPerATioN AND MAiNTeNANce MANuAl
®
TM

verification and Power Up

Figure 9
JSP Diagnostics
R
R
Figure 10
JSP with Counter Option Diagnostics
W A R N I N G ! It is recommended that the cover of the JSP unit along
with its associated cabling be installed prior to applying power. The
monitoring harness, which exits the epoxy and connects to J2 on the
monitor board, contains line voltage when power is applied to the unit.
Apply Power to the JsP unit by closing the overcurrent protection device or
switch feeding the suppressor .
For Compact JSP Units (60, 80, and 100kA)
Verify that all "Protection Available" indicating lights are illuminated . The
"Protection Available" indicating lights extinguish only upon failure of one or
more phases (indicating an alarm condition) .
For Standard JSP Units (120, 160, 200, 240, 300, and 400) or
-M (60, 80 and 100kA)
Verify that all "Protection Available" indicating lights are illuminated . The
"Protection Available" lights extinguish only upon failure of one or more phases
(indicating an alarm condition) .
Audible alarm should not operate under normal conditions . The audible alarm
can be "muted" by pressing the "AlArM sileNce" button, which subsequently
will illuminate the "AlArM sileNceD" light . Pressing the "AlArM sileNce"
button again will enable the audible alarm .
CAUTION: Pressing the "ALARM SILeNCe" button when the alarm
has not triggered will prevent the audible alarm from sounding during
R
a failure.
R
For JSP Units with surge counter option
(Not available on 60, 80 and 100kA)
The number of surges detected by the sPD is displayed on an eight digit
lcD display on the front of the JsP door . The lcD counter is battery backed
to maintain the number of surges even during a power loss . Press the reset
button on the counter to reset the surge count .
R
R
10