Optional Communication Cards

8.1 DCE (Dry Contact) card

8.1.1
The pin assignments of 10-Pin Terminal
1
2
3
4
4
1  N/A
2  Utility Abnormal
3  Utility Normal
4  AVR On
5  Battery Low
6  N/A
7  N/A
8  Common
9  Shutdown UPS positive(+ ) signal
10  Shutdown UPS Negative( - ) signal
8.1.2
The shutdown function will be activated, after a +6~+25Vdc is put
between pin 9 and pin 10 for 5 seconds.
8.1.3
The capacity of each relay contact is 40Vdc/25mA.
8.1.4
Installation Position
Optional Slot.
8.1.5
Flexible signal output for N.C.(Normal Close) or N.O.(Normal Open)
contact by shorting pin1-2 or pin2-3 form JP1-5.
8.1.6
The shutdown function will be enabled in 1 minute after blackout
occurs if the pin1-2 of both CN1 and CN6 are shorted by cap. Or,
the shutdown function can only be enabled by pin9-10 of CN3 if the
pin2-3 of both CN1 and CN6 are shorted by cap.
5
6
7
8
9
10
30

8.2 SNMP Web Card - Ethernet

8.2.1. For installation, please refer to the user's manual attached with the card.
8.2.2. Installation Position:Optional Slot
31