Main Components - Samsung AEN160YDEHA Installation Manual

Air to water heat pump -split hydro unit
Hide thumbs Also See for AEN160YDEHA:
Table of Contents

Advertisement

Main components

No.
Name
1
Air vent 3/8"
2
Backup heater thermal fuse
3
Backup heater thermostat
4
Backup Heater Element
5
Drain Hose
6
Flow switch
7
Water pump
8
Manometer
9
Water outlet pipe
10
Drain valves
11
Service valve(L)
12
Service valve(R)
13
Water inlet pipe
14
Refrigerant pipe
15
Refrigerant pipe
16
Wire for controller
17
Expansion Vessel
18
Plate heat exchanger
19
LED display
20
Control box
21
Pressure relief valve
1
2
3
4
5
6
7
8
9
10
11
BSPP male 3/8"
Thermal cut out 94°C (+0, -6°C)
Disc. 65°C ±4°C
Incoloy 800, 4/6kW, 230V AC 50Hz
12/16LPM ±1.5LPM
1P-230V-50Hz, 46LPM x 54kPa
ø48, 0~4 bar
BSPP male, 1-1/4"
BSPP male, 1-1/4"
BSPP male, 1-1/4"
BSPP male, 1-1/4"
ø9.52(3/8")
ø15.88(5/8")
length 15m
8 Liter, Pre-charge gas : 0.1 MPa, N2, BSPP male, 3/8"
0.3 MPa, BSPP 1/2"
21
20
19
18
17
16
15
14
13
12
Note
9
E-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents