4.5.3 Table "Adjustable Parameters"

Following table shows the standard values (factory set), adjustment ranges and steps:
Display1
Designation
nominal value of output

voltage Uo
monitoring threshold of

output voltage low Uo<
Monitoring threshold of
 
output voltage high
Uo>
switch off threshold
 
input voltage high Ui>
switch off threshold

input voltage low Ui<
switch on again
threshold input voltage

low Ui<
CAN Address

*When adjusting the threshold values with up/down keys, the moving dot shows the actual value according to
the example (this applies only to the 0.25 steps):
Example:

corresponds to 230.0

corresponds to 230.25

corresponds to 230.5

corresponds to 230.75
With each click at the UP/Down keys the dot moves. After four times clicking (4/4), the voltage value is
increased (or decreased) for 1V.
©2009. ELTEK VALERE DEUTSCHLAND GmbH.
Factory setting
Range
230 [V
]
200...255
AC
207 [V
]
180...230
AC
253 [V
]
230...270
AC
48/60V: 75 [V
]
0...80
DC
108V: 130
0...135
48V: 41 [V
]
41...80
DC
60V: 51 [V
]
41...80
DC
108V: 92 [V
]
90...110
DC
48V: 45 [V
]
41...80
DC
60V: 56 [V
]
41...80
DC
108V: 96 [V
]
90...110
DC
001
Step
0,25 [V] *
1,0 [V]
1,0 [V]
0,1 [V]
0,25 [V]*
0,1 [V]
0,1 [V]
0,25 [V]*
0,1 [V]
0,1 [V]
0,25 [V]*
1
UM_UNVF_ E_R2.0