Lynx Model LX-85A
Press "SELECT" button for viewing different modes on "MODE DISPLAY"
MODE
DISPLAY
blinking
blinking
blinking
NOTE:
1-
For space heating mode "0" (boilers not utilizing outdoor sensor))
2-
For DHW mode "2" (storage tank with Aquastat)
3-
For DHW mode "1" (storage tank with sensor)
Table 4
VIEWING AND CHANGING TEMPERATURES
DESCRIPTION & TEMPERATURE DISPLAY
Space heating supply water temperature could be changed by pressing
"Up/Down" button. Settable from 32°–85°C (90°–185°F)
(steps of 1 F). The default value is 80°C (176°F).
Domestic hot water supply temperature could be changed by
pressing"Up/Down" button. Settable from 40°–85°C (104°–185°F)
(steps of 1 F). The default value is 80°C (176°F)
Domestic hot water tank temperature could be changed by
pressing "Up/Down" button. Settable from 32°–71°C (90°–160°F)
(steps of 1 F). The default value is 60°C (140°F).
Temperature display shows actual supply water temperature.
Temperature display shows actual return water temperature.
Temperature display shows actual DHW tank temperature.
(if the water tank is equipped with sensor).
Temperature display shows actual flue gas temperature.
Temperature display shows actual outside temperature.
Press "Enter" button to store.
(see note 1)
Press "Enter" button to store.
(see note 2)
Press "Enter" button to store.
(see note 3)
(if outdoor sensor is used)