Honeywell VisionPro TH8000 Series Operating Manual page 41

Visionpro yh8000 series touchscreen programmable thermostat
Hide thumbs Also See for VisionPro TH8000 Series:

Advertisement

VisionPRO"'" THBDDD Series
Installer setup
,
Setup functions
Settings
&
Options
(factory default in bold)
0500
Furnace filter
change reminder
0
1
2
3
4
5
6
Off
1 O-day run time (about 1 month)
30-day run time (about 3 months)
60-day run time (about 6 months)
90-day run time (about 9 months)
120-day run time (about 1 year)
365-day run time (about 3 years)
0510
Humidifier pad
change reminder
0
1
2
3
Off
90 calendar days
180 calendar days
365 calendar days
0520
UV lamp change
reminder
0
1
Off
365 calendar days
0530
Adaptive Intelligent
RecoveryTM
1
0
On
Off
**
See page 11
0540
Program periods
4
2
4 program periods (Wake, Leave, Return, Sleep)
2 program periods (Wake, Sleep)
0580
Compressor
protection
5
5 minute compressor off time
**
See page 11
[Other options: 0, 1, 2, 3 or 4-minute off time]
0600
Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40-89°F (4°C to 32°C)]
0610
Cool temperature
range stop
50 Min. cool temperature setting is 50°F (10°C)
[Other options: 51-99°F (11°C to 37°C)]
0640
Clock format
12 12-hour time (i.e., "3:30 pm")
24 24-hour time (i.e., "15:30")
0650
Extended fan
timer (heat)
0
90
Off
Fan runs for 90 seconds after call for heat ends
0660
Extended fan
timer (cool)
0
90
Off
Fan runs for 90 seconds after call for cooling ends
0670
Keypad lock
0
1
2
Keypad unlocked (fully functional)
Partially locked (access to temperature settings only)
Fully locked
0680
Heat temperature
control
2
1
3
Standard temperature control (recommended)
Choose if room is warmer than set temperature
Choose if room does not reach set temperature
0690
Cool temperature
control
2
1
3
Standard temperature control (recommended)
Choose if room is cooler than set temperature
Choose if room does not reach set temperature
0700
Temperature
display offset
0
Thermostat displays actual room temperature
[Other options: -3, -2, -1,1,2, 3°F offset (-1.5°C to 1.5°C)
0710
RESET
0
1
No reset
Reset installer options & program schedule to factory
default (only date and time settings are retained)
9

Advertisement

loading

This manual is also suitable for: