Installation Guide
Wiring
Wiring guide-conventional systems
Shaded areas below apply
Q.!lbl
to TH8320/TH8321.
1H/1C System (1 transformer)
Rc
3
Power [1]
R
[R+Rc JOined by jumper]
W
Heat relay
Y
Compressor contactor
G
Fan relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
Heat Only System
Rc
3
Power [1]
R
[R+Rc JOined by jumper]
W
Heat relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
Heat Only System (Series 20)
Rc
3
[R+Rc joined by jumper]
R
Senes 20 valve terminal "R" [1]
W
Series 20 valve terminal "8"
Y
Series 20 valve terminal "W"
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
2H/2C
System (1 transformer)
Y2
Cool relay 2
W2
Heat relay 2
Power.
[1]
tR+Rc
joined
by jumper]
w
Heatrelay
1
Y
.. Cool relaY
1
Fan relay
c
24VAC common [3]
S1
... Qptionaloutdoor/remote sensor
S2
Optional outdoor/remote sensor
See [notes] below
1H/1C System (2 transformers)
Rc
Power (cooling transformer) [1, 2]
R
Power (heating transformer) [1, 2]
W
Heat relay
Y
Compressor contactor
G
Fan relay
C
24VAC common [3, 4]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
Heat Only System
With
Fan
Power [1]
[R+Rc joined by jumper]
W
Heat relay
G
Fan relay
c
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
Cool Only System
Rc
3
Power [11
R
[R+Rc JOined by Jumper]
Y
Compressor contactor
G
Fan relay
C
24VAC common [3]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
2H/2C
System
(2
transformers)
Y2
Cool relay 2
W2
Heat relay 2 .
Rc
Power (cooling transformer) [1,
2]
R
Power (heating transformer) [1, 2]
W
Heat relay 1
y
C991 relay
1
G
Fan relay
c.
.
24VAC common [3, 4]
S1
Optional outdoor/remote sensor
S2
Optional outdoor/remote sensor
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Remove jumper for 2-transformer systems.
[3] Optional 24VAC common connection.
[4] Common connection must come from cooling transformer.