6.Ac/Heat Pump Rpm Max; 7.Defrost Fan Delay; 8.Brownout Disable; 9.Low Air Multiplier - Bryant Evolution Connex SYSTXBBECW01-A Installation Instructions Manual

Evolution connex control
Hide thumbs Also See for Evolution Connex SYSTXBBECW01-A:
Table of Contents

Advertisement

6.3.4.6.
AC/Heat Pump RPM Max
Used with variable capacity heat pumps, this option clamps the operating speed
of the heat pump to this maximum value. Used to reduce operating noise while in
high heating capacity. Reducing this value will reduce the heating capacity of the
heat pump. After the selection is made, touch SAVE.
AC Heat Pump Max RPM: Adjustable from 4500 – 7000
S
Default = 7000 RPM
d
6.3.4.7.
Defrost Fan Delay
Turns on the outdoor unit fan at the end of a defrost cycle for approximately 12
seconds. This helps to reduce any nuisance refrigerant noise caused by the
switching reversing valve. This setup is only available on communicating heat
pumps. After the selection is made, touch SAVE.
Defrost Fan Delay: Yes or No
S
Default = No
d
6.3.4.8.
Brownout Disable
This option turns off the high voltage brownout detection function in the outdoor
unit control. This setup is only available on communicating heat pumps. After the
selection is made, touch SAVE.
Brownout Disable: On or Off
S
Default = Off
d
6.3.4.9
Low Air Multiplier
Adjusts the airflow speed on non- - communicating two- - stage units. Choose 0.65 for
units with a Bristol compressor, choose 0.80 (default) for units with a Copeland
scroll compressor.
43