Combustion Air And Ventilation; Combustion Air And Ventilation For Appliances In Unconfined Spaces; Combustion Air And Ventilation For Appliances In Confined Spaces - Kenmore 153.335863 Owner's Manual

Power vent gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Combustion
Air and Ventilation
for Appliances
Located
in
Unconfined
Spaces
Unconfined
Space is a space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour of the aggregate input rating of all appli-
ances installed in that space. Rooms communicating
directly with the
space in which the appliances are installed, through openings not fur-
nished with doors, are considered a part of the unconfined space.
In unconfined
spaces in buildings, infiltration
may be adequate to
provide air for combustion,
ventilation
and dilution
of flue gases.
However, in buildings of tight construction
(for example, weather
stripping, heavily insuhted, caulked, vapor barrier, etc.), additional air
may need to be provided using the methods described in Combustion
Air and Ventilation for Appliances Located in Confined Spaces.
Combustion Air and Ventilation
for Appliances Located in
Confined Spaces
Confined Space is a space whose volume is less than 50 cubic feet per
1,000 Btu per hour of the a_regate
input rating of all appliances
installed in that space.
a. ALL AIR FROM INSIDE BUILDINGS:
(See Page 9 Figure 1, and Figure 6 below)
The confined space shall be provided with two permanent open-
ings communicating
directly with an additional room(s) of suffi-
cient volume so that the combined volume of all spaces meets the
criteria for an unconfined space. The total input of all gas utiliza-
tion equipment installed in the combined space shall be considered
in making this determination.
Each opening shall have a minimum
free area of one square inch per 1,000 BTU per hour of the total
input rating of all gas utilization equipment in the confined space,
but not less than 100 square inches. One opening shall commence
within 12 inches of the top and one commencing within 12 inches
of the bottom of the enclosure.
J Figure 6 J
_
VEr_Tm
,o .....
b. ALL AIR FROM OUTDOORS:
(see Figures 7-9)
The confined space shall be provided with two permanent open-
ings, one commencing
within 12 inches of the top and one com-
mencing
within
12 inches from the bottom
of the enclosure.
The openings shall communicate
directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate
with
the outdoors.
Figure 7 ]
I2
1. When directly communicating
with the outdoors, each opening
shall have a minimum
free area of 1 square inch per 4,000 BTU
per hour of total input rating of all equipment
in the enclosure.
(See Figure 7.)
2. When communicating
with the outdoors
through vertical ducts,
each opening shall have a minimum
flee area of 1 square inch
per 4,000 BTU per hour of total input rating of all equipment in
the endosure.
(See Figure 8.)
Figure
8 ]
vEr_TKAhON LOUVERS
4each er_ oramc]
AIR OUTLET
{ends 1, a_e
_le,00
WATE¢_
H_ATER
i
i
i
i
i
i
i
i
i
I
I
I
I
I
I
I
llliJik
I
I_1_
3. When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum flee area of 1 square
inch per 2,000 BTU per hour of total input rating of all equip-
ment in the enclosure. (See Figure 9.)
Figure 9 ]
OUTLET AIR DUCT
Ol/TP'_OFI$
WATER
tNLE
illllllllllll'l'l'l
'
_'_l_l_II
4. When ducts are used, they shatl be of the same cross-sectional area
as the free area of the openings to which they connect. The mini-
mum short side dimension of rectangular air ducts shall not be
less than 3 inches. (See Figure 9.)
5. Louvers and Grilles: In calculating free area, consideration shall be
given to the blocking effect of louvers, grilles or screens protect-
ing openings. Screens used shall not be smaller than ¼ inch mesh.
If the free area through a design of louver or grille is known, it
should be used in calculating the size opening required to provide
the free area specified. If the design and free area is not known, it
may be assumed that wood louvers will be 20-25 percent free area
and metal louvers and grilles will have 60-75 percent free area.
Louvers and grilles shall be fixed in the open position or inter-
locked with the equipment so that they are opened automatically
during equipment operation.
6. Special
Conditions
Created
by Mechanical
Exhausting
or
Fireplaces: Operation
of exhaust Fans, ventilation systems, clothes
dryers or fireplaces may create conditions
requiring special atten-
tion to avokl unsatisfactory operation of installed gas utilization
equipment.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents