Venting Clearances - Kenmore 153.335863 Owner's Manual

Power vent gas water heater
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
Venting Through Roof- Clearances
0" clearance for 3" (or optional 2") PVC, ABS, or CPVC Schedule
40 piping from combustible surfaces.
The Power Vent outlet terminal shall terminate at least 18" above
the roof surface. Figure 5.
The location selection must provide clearances for servicing and
proper operation of the water heater. Figure4,
The venting system must be installed in a manner which allows
inspection of the installation of the venting pipes and joints as
well as periodic inspection after installation as required by ANSI
Standards.
18"
Figure 5_
11