Adding Refrigerant
22
E-
How to Calculate the Quantity of Adding Refrigerant
If you have used more than 5m(16.4 ft.), add "A" of refrigerant for extra
meter. (For maximum piping length and height, refer to page 16).
The quantity of additional refrigerant is variable according to the installation
situation. Thus, make sure the outdoor unit situation before adding
refrigerant. This operation can only be performed by a qualified refrigeration
specialist.
Model
RFPC012CBM0
RFPC015CBM0
RFPC020CBM0
RFPH025CBM0
i.e. 1 indoor unit
Piping length
"a"
5m/16.45ft
7m/23ft
0.7oz={(23-16.4) x 0.11oz}
i.e. 2 indoor units
Piping length
a
b
c
a+b+c
3m/9.8ft
1m/3.3ft
1m/3.3ft
5m/16.45ft
3m/9.8ft
2m/6.6ft
4m/13.15ft
9m/29.55ft
"A"
10g/m 0.11oz/ft
15g/m 0.16oz/ft
20g/m 0.22oz/ft
25g/m 0.27oz/ft
Additional charging amount
RFPC012CBM0
RFPC020CBM0
0
20g={(7-5) x 10g}
40g{(7-5) x 20g}
0.4oz={(23-16.4) x 0.22oz}
Additional charging amount
RFPC012CBM0
0
40g={(9-5) x 10g}
1.4oz={(29.5-16.4) x 0.11oz}
0
RFPC020CBM0
0
80g={(9-5) x 20g}
2.8oz={(29.5-16.4) x 0.22oz}