Adding Refrigerant - Samsung AFPCC052CA0 Installation Manual

Cooling only system air conditioner
Hide thumbs Also See for AFPCC052CA0:
Table of Contents

Advertisement

Adding Refrigerant

The outdoor unit is loaded with sufficient refrigerant for the standard
piping. Thus, refrigerant must be added if the piping is lengthened.
This operation can only be performed by a qualified refrigeration
specialist. For quantity of adding refrigerant, refer to page 22.
1
Check that the stop valve is closed entirely.
2
Charge the refrigerant through the service port of liquid stop valve.
N N
o o
t t
e e
Do not charge the refrigerant through the gas side service port.
N N
o o
t t
e e
3
If you cannot charge the refrigerant according to the upper steps,
following these:
3-1 Open both liquid stop valve and gas stop valve.
3-2 Operate the air conditioner by pressing the K2 key on the outdoor
unit PCB.
3-3 About 30 minutes later, charge the refrigerant through the service
port of gas stop valve.
N N
o o
t t
e e
If necessary, refer to the pressure table classified by outdoor
N N
o o
t t
e e
temperature.
Outdoor unit
R
22
Balance
Vacuum pump
Liquid side stop valve(service port)
Gas side stop valve(service port)
Indoor unit
1
2
21