Servicing; Annual Servicing - Potterton Gold 24 HE Installation & Service Instructions Manual

Gold combi he series
Table of Contents

Advertisement

Case Front Panel
Fig. 40
Facia Panel
Securing Screws
Inner Door
Panel
32
Fig. 41
Condensate
Trap
Fig. 41a

11.0 SERVICING

11 .1

Annual Servicing

1. For reasons of safety and economy, it is
recommended that the boiler is serviced annually.
Servicing must be performed by a competent person.
If a combustion analyser is available the CO
checked and adjusted - see Section 13.0.
2. After servicing, complete the relevant Service
Interval Record section of the Benchmark
Commissioning Checklist at the rear of this publication.
3. Ensure that the boiler is cool.
4. Ensure that both the gas and electrical supplies
to the boiler are isolated.
5. Slacken the screws securing the facia panel. Lift the
outercase panel so that its securing tabs are clear of
the facia. Remove the panel, allowing the facia to hinge
down (Fig. 40).
6. Remove the screws securing the inner door panel.
Lift the panel slightly to disengage it from the studs on
top of the case (Fig. 41).
7. Unscrew the sump from the bottom of the
condensate trap assembly (Fig. 41a).
8. Remove any deposits from the sump and trap. Clean
as necessary and replace the sump.
Sump
can be
2
Publication No. 5116282