Troubleshooting Guide; Start Up Conditions; Thermal Expansion; Strange Sounds - Kenmore 153.31206 Owner's Manual

Electric water heater
Table of Contents

Advertisement

Troubleshooting
Guide
Start
Up Conditions
THERMAL
EXPANSION
Water supply systems may, because of such events as high line
pressure, frequent cut-off's, the effects of water hammer among
others, have installed devices such as pressure reducing valves,
check valves, back flow preventers, etc.-to control these types of
problems• When these devices are not equipped with an internal
by-pass, and no other measures are taken, the devices cause the
water system to be closed• As water is heated, it expands (ther-
mal ex_,ansion) and closed systems do not allow for the expan-
sion of heated water.
The water within the water heater tank expands as it is heated and
increases the pressure of the water system• If the relieving point of
the water heater's temperature-pressure
relief valve is reached, the
valve will relieve the excess pressure. The temperature-pressure
relief valve is not intended for the constant relief of thermal
expansion. This is an unacceptable condition and must be cor-
rected.
It is recommended that any devices installed which could createa
closed system have a by-pass and/or the system have an expan-
sion tank to relieve the pressure built by thermal expansion.
Thermal expansion tanks are available from Sears stores and
through the Sears Service Centers. Contact the local plumbing
inspector, water supplier and/or the Sears Service Center for
assistancein controlling these situations.
Thermal
Expansion
Tank Specifications
Model TankCapacity
Oimensionsin nches
Pipe Fitting
Number
InGallons
Diameter
Length
On Tank
153.331020
2
8inches
12_inches
_"Male
153.331050
5
11 inches
14_inches
_"Male
HOT
COLD
WATER HEATER
COLD WATER
INLET FITTING
HOT
WATER HEATER
O)
• COLD WATER
PRESSURE
INLET FI'I-NNG
REDUCING
VALVE W ITH
BY.PASS
WATER
SHUTOFF
RECOMMENDED
INSTALLATION
(VERTICAL MOUNTING)
FLOOR,CEILING
JOIST,ETC.
STRAPPING
(1)
EXPANSION
0)
PRESSURE
REDUCING
INLET COLD
VALVE WITH
WATER
BY-PASS
SHUTOFF
Expansion
Tank Sizing Chart
Water Heater Capacity (Gallons)
Inlet*
Water
Pressure
i 40psi
50psi
60psi
70psi
80psi
Expansion
30
40
50
66
82
Tank
2
2
2
5
5
Capacity
2
2
2
5
5
Needed
2
2
5
5
5
2
2
5
5
5
2
5
5
5
5
*Highest recorded inlet water pressure in a 24 hour period or
regulated water pressure.
NOTE:
Expansion
tanks are pre-charged
with a 40 psi air
charge. If the inlet water pressure is higher
than 40 psi, the
expansion
tank's air pressure must be adjusted to match that
pressure, but must not be higher than 80 psi.
PRESSURE GAUGE
ALTERNATE
RECOMMENDED
INSTALLATION
(HORIZONTAL M OUNTING)
STRANGE
SOUNDS
Possible noises due to expansion and contraction of some metal
parts during periods of heat-up and cool-down do not represent
harmfial or dangerous conditions•