Wiring Diagram (DC48GTVA,DC60GTVA)
MAIN PCB
Float Switch
Drain Pump
(Optional)
1(L) 2(N) 3(C)
Power
Cable Specifications
The following electrical characteristics must be respected.
MODEL
Power
Circuit breaker
Indoor unit power cable
Wired remote controller power
& communication cable
20m or less
Power cable
50m or less
Receiver &
Display Unit
(Optional)
Indoor Unit
Vc
Vc
F1
F2
V1
V2
Signal
1(L)
2(N)
Outdoor Unit
DC48GTVA(X),DC60GTVA(X)
3ø 380-415V~, 50Hz
20A
1.25mm
(CV, 4 wire)
2
0.5~0.75mm
(CV, 2 wire)
2
2.0mm
(CV, 5 wire)
2
2.5mm
(CV, 5 wire)
2
F3
F4
Wired
Remote
Controller
3
3(C)
The power cables are not
supplied with the air
conditioner.
The user should purchase
them separately.
MAIN POWER
380 - 415V~, 50H
ø
z
Note